Document #50066 Rev. D2 12/03/02 P/N 50066:D2
37
Programming Options
Secondary Central Station Number Communication Format (42)
One location is needed to select the Communication Format for the secondary phone number. Address 42 is used for
this purpose. The default (factory setting) for this address is '
A
' (
42_A
), which is 4+2 Standard, 1800 Hz 'Carrier',
2300 Hz 'ack'. You may enter 0 through D in place of the default, then press the
[ENTER/STORE]
key. Choose
from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Not used
F: Not used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format cho-
sen, the control panel automatically programs all of the event codes. See Table 3-1 , Table 3-2 , Table 3-3 and Table
3-4 .
CAUTION!
Default entries for event codes (as shown in Table 3-1 through Table 3-4 ) are programmed into memory
each time address 42 is altered. Be certain to double check entries after programming the Zone Functions, addresses
57 - 61. Program the Format first then program the Zone(s) Function.
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 42, the data in Table 3-3 is automatically programmed for the
Secondary Central Station phone number event codes. Enter '0' for the setting to disable the report.
TABLE 3-3:
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded - Secondary
Address
Description
Setting
198
Secondary # Zone 1 Alarm Code
1
199
Secondary # Zone 2 Alarm Code
1
200
Secondary # Zone 3 Alarm Code
1
201
Secondary # Zone 4 Alarm Code
1
202
Secondary # Zone 5 Alarm Code
1
203
Secondary # Zone 1 Disabled Code
F
204
Secondary # Zone 2 Disabled Code
F
205
Secondary # Zone 3 Disabled Code
F
206
Secondary # Zone 4 Disabled Code
F
207
Secondary # Zone 5 Disabled Code
F
208
Secondary # Drill Code
9
209
Secondary # AC Fault Code
F
210
Secondary # Zone 1 Fault Code
F
211
Secondary # Zone 2 Fault Code
F
212
Secondary # Zone 3 Fault Code
F
213
Secondary # Zone 4 Fault Code
F
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...