Operation
50
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
4.3.3 System Supervisory Condition Response
Program zones for supervisory in applications where a waterflow sensing device has been employed and the wiring to
the waterflow valve and/or tamper switch is to be monitored. If the wiring has been cut or the tamper switch has been
activated, a supervisory alarm condition will occur.
When a supervisory condition occurs, the control panel will:
• Blink the supervisory LED (½ second On, ½ second Off)
• Activate the supervisory relay(s) if programmed
• Display the following message:
SUPX
where X is the zone number
• Communicate the supervisory condition to the Central Station
• Store the 'supervisory' message in the History file
• Pulse the piezo sounder at ½ second on and ½ second off rate
• Turn on the annunciator zone LED and pulse the annunciator piezo
4.3.4 System Supervisory Restoral Response
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed), the
control panel will perform the following:
• Turn off the supervisory LED
• Deactivate the supervisory relay(s) if programmed
• Clear the display of the
SUP
message
• Communicate a supervisory restoral message to the Central Station
• Turn off the piezo sounder
• Turn off the annunciator zone LED and annunciator piezo sounder
Note that for any zone programmed for supervisory autoresettable, the Reset key does not need to be pressed to clear
the zone supervisory condition.
4.3.5 Trouble Condition Response
The control panel will perform the following upon detection of one or more trouble conditions:
• Blink the trouble LED (1 second on, 1 second off)
• Activate the trouble relay(s) if programmed
• Display the appropriate trouble message(s) in priority fashion from the highest priority to the lowest.
Note
that the Up arrow, Down arrow or 1st Event key must be pressed to view the messages
• Communicate the trouble conditions to the Central Station
• Store the trouble conditions in the History file
• Sound the piezo sounder (1 second on, 1 second off)
• Blink the annunciator trouble LED and pulse the piezo sounder
Note that when AC brownout occurs, the AC LED is turned off and the trouble LED blinks. Should the brownout con-
dition remain, it will be transmitted to the Central Station after a delay (see program address 64).
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...