Programming Options
42
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Zone 1 Function Selection (57)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Zone 2 Function Selection (58)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Zone 3 Function Selection (59)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory, '4' for supervisory autoresettable, '5' for waterflow silenceable or '6' for waterflow
nonsilenceable.
Zone 4 Function Selection (60)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Zone 5 Function Selection (61)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted event
codes (note in Table 3-1 through Table 3-4 ) to be automatically changed. The defaulted code of '1' is changed to '8'
for Formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express. The defaulted codes of 11, 12,
13, 14 and 15 are changed to 81, 82, 83, 84 and 85 accordingly for Formats 4+2 Standard and 4+2 Express.
Waterflow Retard Timer (62-63)
A delay may be added prior to declaring a waterflow type of alarm. Delays up to 89 seconds are allowed. The
default for addresses 62 and 63 are '00' for no additional delay. Valid entries for address 62 are '0' to '8' and for
address 63 '0' to '9.' Program an entry into these addresses only if entering a '5' or '6' in address 59.
Be careful to
include any built-in delays of the waterflow device.
AC Loss Reporting Delay (64)
Enter a digit of '1' to '9' or 'A' to 'F' corresponding to the number of hours to be delayed in reporting the loss of AC
power. The factory default setting is '0' for 6 hour delay. If 24 hour battery backup is being employed, select from
choices '0' to '6'. If 60 hour battery backup is used, select from choices '7' to 'F'. Selections are:
0 = 6 hour delay
1 = 7 hour delay
2 = 8 hour delay
3 = 9 hour delay
4 = 10 hour delay
5 = 11 hour delay
6 = 12 hour delay
7 = 15 hour delay
8 = 16 hour delay
9 = 17 hour delay
A = 18 hour delay
B = 19 hour delay
C = 20 hour delay
D = 21 hour delay
E = 22 hour delay
F = 23 hour delay
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...