![Fire-Lite Alarms MS-5024 Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/fire-lite-alarms/ms-5024/ms-5024_product-description_2291100028.webp)
Optional Boards
28
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
2.8
Optional Boards
2.8.1 ADM-24 Annunciator Driver Module
The ADM-24 supports the RZA-5F Remote Annunciator. The wiring is supervised for open conditions by this mod-
ule. The Annunciator Driver Module mounts to J3 in the upper right corner of the main circuit board.
2.8.2 RZA-5F Remote Annunciator
The RZA-5F mounts on a standard single-gang electri-
cal box and provides LED indication of the following:
• Alarm Zone 1 (red LED)
• Alarm Zone 2 (red LED)
• Alarm Zone 3 (red LED)
• Alarm Zone 4 (red LED)
• Alarm Zone 5 (red LED)
• System Trouble (yellow LED)
The remote annunciator provides individual zone
alarm LEDs, a system trouble LED, a piezo sounder
and a remote sounder shut off switch. All LEDs and
their wiring are supervised for open conditions. Any
open condition will cause the System Trouble LED to
illuminate.
Note that the RZA-5F requires the use of an ADM-24
Annunciator Drive Module. Only one RZA-5F/ADM-
24 combination is allowed per system.
FIGURE 2-10:
ADM-24
Main Board
ADM-24
Connector located on back of board
Standoff
FIGURE 2-11:
RZA-5F
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...