CHAPTER 4
Operating Instructions
The MS-5024 has five modes of operation; Normal, Program, Walktest, Troubleshoot and History. Upon initial
power-up, the system will be in Normal Mode. This chapter discusses operation of the control panel in the Normal
Mode.
4.1
Switches
This section describes the function switches in Normal Mode.
4.1.1 Reset
The Reset Switch resets the system and any smoke detectors. If the Reset Switch is pressed, the control panel will:
• Clear the display and status LEDs
• Turn off the Notification Appliance Circuits
• Reset all zones by temporarily removing power
• Silence the on-board piezo sounder
• Store 'reset' message in the History file
• Restore the programmable relays to normal
• Temporarily remove power from the resettable power output TB4 Terminals 3 & 4
Upon release of the Reset Switch, the display will read
rES_
for six seconds. Any alarm, supervisory or trouble con-
dition that exists after system reset will resound the system, reactivating normal system activity.
4.1.2 Silence
If the Silence Switch is pressed:
• The silenceable Notification Appliance Circuits will be turned Off
• The silence LED will be turned On
• The piezo sounder will be shut Off
• 'System Silenced' message will be stored in the History file
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...