Document #50066 Rev. D2 12/03/02 P/N 50066:D2
43
Programming Options
Alarm Presignal (65)
Positive Alarm Sequence is used to delay Notification Appliance Circuit(s) activation while allowing for visual veri-
fication by a person. Once a zone triggers an alarm, the mainboard piezo and the annunciator piezo turn on steady,
the display indicates the activated zone, the alarm LED blinks and the Notification Appliance Circuits are held off for
15 seconds. During this time, if the silence switch is pressed, the notification appliances may be held off for up to
three minutes (see Alarm Presignal Delay Timer Address 66-68). After the programmed delay period, the notifica-
tion appliances will activate.
Alarm Presignal does not function for zones defined as waterflow or supervisory.
The
factory default is '0' for no Alarm Presignal. Enter '1' to select Alarm Presignal. During Alarm Presignal, access to
other modes is prevented and the communicator will not transmit a signal to the Central Station signifying that the
Alarm Presignal has been initiated.
Alarm Presignal Delay Timer (66-68)
The Alarm Presignal timer is factory set to 120 seconds (two minutes), with address 66 set to '1', address 67 set to '2'
and address 68 set to '0'. The timer may be programmed from 0 to 179 seconds. Location 65 must be set to '1' to
enable Alarm Presignal.
Notification Appliance Circuit #1 Enable (69)
Notification Appliance Circuit #1 may be programmed to '0' for silenceable, '1' for nonsilenceable or '2' for disabled.
The factory default setting is '0' for silenceable.
Consult the local Authority Having Jurisdiction (AHJ) prior to
altering this address.
Silence Inhibit Notification Appliance Circuit #1 (70)
Setting address 70 to '1' prevents silencing of Notification Appliance Circuit #1 and the on-board piezo sounder for
one minute after an alarm. The factory default setting is '0' for no silence inhibit of Notification Appliance Circuit #1.
Autosilence Notification Appliance Circuit #1 (71)
Notification Appliance Circuit #1 may be autosilenced after a programmed time interval between 5 and 30 minutes.
Enter '1' for 5 minute autosilence, '2' for 10 minute autosilence, '3' for 15 minute autosilence, '4' for 20 minute autosi-
lence, '5' for 25 minute autosilence or '6' for 30 minute autosilence. The factory default setting is '0' for no
autosilence.
Coding Notification Appliance Circuit #1 (72)
Coding of Notification Appliance Circuit #1 can be programmed by selecting '1' for March Time (120 ppm), '2' for
California (10 seconds On, 5 seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second
Off, ½ second On, 1½ second Off). The factory default setting is '0' for steady (no coding).
Notification Appliance Circuit #2 Enable (73)
Notification Appliance Circuit #2 may be programmed to '0' for silenceable, '1' for nonsilenceable or '2' for disabled.
The factory default setting is '0' for silenceable.
Consult the local Authority Having Jurisdiction (AHJ) prior to
altering this address.
Silence Inhibit Notification Appliance Circuit #2 (74)
Setting address 74 to '1' prevents silencing of Notification Appliance Circuit #2 and the on-board piezo sounder for
one minute after an alarm. The factory default setting is '0' for no silence inhibit of Notification Appliance Circuit #2.
Autosilence Notification Appliance Circuit #2 (75)
Notification Appliance Circuit #2 may be autosilenced after a programmed time interval between 5 and 30 minutes.
Enter '1' for 5 minute autosilence, '2' for 10 minute autosilence, '3' for 15 minute autosilence, '4' for 20 minute autosi-
lence, '5' for 25 minute autosilence or '6' for 30 minute autosilence. The factory default setting is '0' for no
autosilence.
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...