EN
54
• Use the two M8 screws with flat and spring washers (supplied) to
fix the pieces of the bracket together.
• Position the bracket
(03)
perfectly level on the support and use it
as drilling template (consider the overall dimensions of the power
module and the wiring box).
• It is the installer’s responsibility to choose an appropriate number
and distribution of attachment points. The choice must be based
on the type of support (wall, frame or other support), the type
of anchors to be used, and their ability to support 4 times the
inverter’s weight (4x125Kg/276lbs=500Kg/1104lbs for all models).
• Depending on the type of anchor chosen, drill the required holes
to mount the bracket
(03)
. The pictures shown the recommended
minimum fixing point depending to the type of support.
• Attach the bracket
(03)
to the support with at least 6 attachment
screws (shown in
YELLOW
) or at least 6 frame fixing bracket for
frame mounting (shown in
BLUE
).
Wall mounting minimum fixing points
Frame mounting (2 supports) minimum fixing points
Frame mounting (3 supports) minimum fixing points
• In case of use of “frame fixing brackets” (see picture below as
example) it will be possible to fix the bracket to the frame structure
without drill any additional holes.
• Fix the bracket
(03)
to the support.
5.5 Assembly the Inverter to the bracket
ATTENTION –
A
Handling and installation operations shall be
performed only by using the special tools and accessories
provided with “PVS Installation Kit” that have to be ordered
separately. The use of these equipment are mandatory to
safely install the inverter.
• Lift the wiring box up to the bracket
(03)
(using the handles
(04)
or
M8 eyebolts) and insert the heads of the two rear pins for bracket
assembly
(13)
(placed on the rear part of the wiring box
(02)
) into