EN
107
• Test the absence of voltage on the DC inputs using the voltage
detector: the voltage absence test on DC side must be carried out
on the positive side string fuses board
(19)
and on negative side
string fuses board
(20)
. The layout of the two boards is provided
below, with reference of the points where the input DC voltage
absence test must be performed. The points are represented by
the faston where the cables (coming from DC switches
(15)
) are
connected.
CH1
CH2
CH3
CH4
CH5
CH6
1A
2A
1B
2B
1C
2C
1D
2D
3A
4A
3B
4B
3C
4C
3D
4D
5A
6A
5B
6B
5C
6C
5D
6D
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
CH1
CH2
CH3
CH4
CH5
CH6
1A
2A
1B
2B
1C
2C
1D
2D
3A
4A
3B
4B
3C
4C
3D
4D
5A
6A
5B
6B
5C
6C
5D
6D
PE
For each input channel the measurement must be performed
between: positive to ground, negative to ground, positive to
negative.
Check sequence: Positive to ground (PE)
First point
Second point
1A (+)
PE
1B (+)
PE
1C (+)
PE
1D (+)
PE
2A (+)
PE
2B (+)
PE
2C (+)
PE
2D (+)
PE
3A (+)
PE
3B (+)
PE
3C (+)
PE
3D (+)
PE
4A (+)
PE
4B (+)
PE
4C (+)
PE
4D (+)
PE
5A (+)
PE
5B (+)
PE
5C (+)
PE
5D (+)
PE
6A (+)
PE
6B (+)
PE
6C (+)
PE
6D (+)
PE
Check sequence: Negative to ground (PE)
First point
Second point
1A (-)
PE
1B (-)
PE
1C (-)
PE
1D (-)
PE
2A (-)
PE
2B (-)
PE
2C (-)
PE
2D (-)
PE
3A (-)
PE
3B (-)
PE
3C (-)
PE
3D (-)
PE
4A (-)
PE
4B (-)
PE
4C (-)
PE
4D (-)
PE
5A (-)
PE
5B (-)
PE
5C (-)
PE
5D (-)
PE
6A (-)
PE
6B (-)
PE
6C (-)
PE
6D (-)
PE
Check sequence: Positive to negative
First point
Second point
1A (+)
1A (-)
1B (+)
1B (-)
1C (+)
1C (-)
1D (+)
1D (-)
2A (+)
2A (-)
2B (+)
2B (-)
2C (+)
2C (-)
2D (+)
2D (-)
3A (+)
3A (-)
3B (+)
3B (-)
3C (+)
3C (-)
3D (+)
3D (-)
4A (+)
4A (-)
4B (+)
4B (-)
4C (+)
4C (-)
4D (+)
4D (-)
5A (+)
5A (-)
5B (+)
5B (-)
5C (+)
5C (-)
5D (+)
5D (-)
6A (+)
6A (-)
6B (+)
6B (-)
6C (+)
6C (-)
6D (+)
6D (-)
8.2.4.11 Voltage absence test on AC side (wiring box)
• Visually inspect the components to identify the presence of
any overheating, signs of electric arcs, failure of the insulating
devices, loosen connections or cables not connected.