CIE-A-200 Control Panel Engineering and Commissioning Manual
26
The correct battery charger settings must be selected for the size of battery used, this is done using DIL
switch S1
– 1 and S1 – 2.
Battery Capacity
Switch S1 - 1
Switch S1 - 2
7Ah
ON
ON
12Ah
OFF
OFF
If these settings are incorrect for the batteries being used it will either cause the batteries to be over charged
or under charged. Incorrect settings could cause damage to the batteries.
Note that batteries are electrically live at all times and great care should be taken to ensure that the terminals
are never presented with a short circuit. Care should be taken at all times, especially during transit, installation
and normal use.
Use caution as there is a risk of explosion if the batteries are replaced by an incorrect type.
Batteries no longer required should be disposed of in a safe and environmentally friendly manner by the
battery manufacturer or a suitable recycling service. They should never be incinerated or placed in normal
rubbish collection facilities. Dispose of used batteries according to the
manufacturer’s instructions.
Fuses 1 and In-Line Battery Fuse
Fuse 1 is located on the backplane PCB, the In-Line battery fuse is located in the battery feed positive line.
Panel Backplane
Label
Description
Fuse
F1
Auxiliary Power
T500 mA
IN-LINE
Battery
F3.15A
S1
– 3: Temperature Probe - Enable / Disable
S1
– 2: Battery Selection
S1
– 1: Battery Selection