CIE-A-200 Control Panel Engineering and Commissioning Manual
42
10. View Edit Attributes
▼
View Edit Attributes
→
Device
This function allows the user to view, and edit if required, the attributes
for each loop device. These
attributes include the device type, serial number, address, zone, description, input, output, detection
and alarm information. You may also read the optical and heat standing levels for Multipoint
detectors. If changes are made, the individual device may be reconfigured to save the longer task of
reconfiguring all devices on that loop.
View Edit Attributes
→
AUX I/O Device
This function allows the user to view and edit the attributes of the auxiliary inputs and outputs of the
devices on the loop.
11. Panel I/O
▼
Panel I/O
→
Monitored Output Settings
This will allow the engineer to view or change the operation of the Monitored O/P settings.
Monitored outputs can be programmed as follows.
NOT CONFIGURED
– O/P will not be active.
SOUNDER OUTPUT
– Operation of O/P will mimic that of a conventional sounder circuit
and will de-activate on silence.
FIRE OUTPUT
– Operation of O/P will mimic that of a fire circuit and will de-activate on reset.
COMMON FAULT
– O/P will active when there is a fault on the panel.
SOUNDER OUTPUT CADENCE - Operation of O/P will mimic that of a conventional sounder
circuit but the voltage out will pulse every 500ms and will de-activate on silence.
Panel I/O
→
Relay Output Settings
This will allow the engineer to view or change the operation of the Relay O/P settings. The Fault
Relay (Relay Output 3) will be fixed as a fault relay and cannot be altered. Relay Outputs 1 & 2 can
be programmed as follows.
NOT CONFIGURED
– O/P will not be active.
FIRE OUTPUT (COMMON)
– Common Fire output where the relay is energised in the fire
condition and will remain so until the system is reset.
ZONE IN FIRE OUTPUT (ZONAL)
– A Zonal Fire Output (a zone must be specified in the
range 1-32) is activated by a Fire in the specified zone. The relay is energised in the fire
condition and will remain so until the system is reset.
COMMON FAULT
– O/P will active when there is a fault on the panel.