CIE-A-200 Control Panel Engineering and Commissioning Manual
11
Cable Entry
The cable entry locations are provided by two rows of knockouts at the top, six on the back and one on the
bottom.
The bottom knockout should be used if the 12Ah battery box is used.
The rear bottom half of the panel must be kept clear for mounting the 7Ah internal batteries.
It is recommended that
fire rated cable glands are used
to ensure that the characteristics of the enclosure
can be maintained adequately.
Mounting Data
Panel Dimensions:
Width x Height
353mm x 333mm
Depth
117mm
Flush Mount Hole Size:
Width x Height (with cradle)
354mm x 334mm
Depth
83mm
Control Panel Assembly
The backboard assembly is attached to the panel back box by two brackets on the bottom of the assembly,
the two brackets hook into the back box. There is a single captive knurled screw in the centre at the top of
the assembly which holds it in.
To fit the backboard assembly, tip the assembly forward and hook the two lower brackets into the back box
then bring the assembly upright and then secure it with the knurled screw.
To refit the front door which houses the panel controls, line up the top & bottom threaded holes in the left
hand side of the door with the hinge bracket on the back box and fit the two hinge screws.
Connect the ribbon cable to the back board and CIE.