*Reducer or increaser ratio (d/D) small diameter divided reducer ratio is d/D = 
4/8 = 1/2. To estimate the equivalent foot length for the fitting, use the smaller 
pipe diameter for the equivalent length figure. Example 4" to 8" reducer; the 
reducer ratio is 1/2 and the smaller pipe diameter is 4". So, from the chart, 
the equivalent length would be 7 feet (see Figure 1). 

Example: 

System Pipe Size = 4" 

Step 1  Two 4" 90° elbows @ 7 feet each = 14 ft. 
Step 2  Ten 2 foot lengths of 4" pipe = 20 ft. 
Step 3  Total equivalent feet = 14 ft. + 20 ft. = 34 ft. 

 

 

INSTALLING SWG-AF POWER VENT  

WARNING:

 

Failure to install, maintain and/or operate the power vent system in accordance with manufacturer's 

instructions can result in conditions which may cause Death, Bodily Injury and/or Property Damage.

 

1.  Remove power vent from box and inspect unit for damage. If the carton has been crushed or mutilated, check unit 

very carefully for damage. Rotate blower wheel to insure that the motor and blower wheel rotate freely. 

DO NOT

 

install if any damage is apparent. Refer to Table 1 (Page 3) to check for proper vent sizing. 

2.  Location of the termination of the venting system should be determined according to in:    

       

United States  

 

NFPA 211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances, the International 
Mechanical Code and / or International Residential Code. The appliance manufacturer's installation 
instructions and /or local codes and the authority having jurisdiction. 

 

See requirements below or refer to installation location, Diagram A (Page 5), for typical locations. 

       

Canada 

  CSA B365 Installation Code for Solid Fuel-Burning Appliances and Equipment and any other federal, 

provincial, local code requirement and the manufacturer’s installation instructions. 

 

See requirements below or refer to installation location, Diagram A (Page 5), for typical locations. 

 

a.  The exit termination of mechanical draft systems shall not be less than 7' above grade when located adjacent to 

public walkways. 

b.  A venting system shall terminate at least 3' above any forced air inlet located within 10'. 
c.  The venting system of other than a direct vent appliance shall terminate at least 4' below, 4' horizontally from or 1' 

above any door, window or gravity air inlet into the building.   

d.  The vent termination point shall not be installed closer than 4' from an inside corner of an L-shaped structure. 
e.  The vent termination should not be mounted directly above, or within 3' horizontally from an oil tank vent or gas 

meter. 

f. 

The bottom of the vent terminal outlet shall be at least 12” above finished grade or typical yearly snow line. If this 
is not possible use the SWG-VR-AF series power vent riser. 

g.  The area in front of power vent and 4’ either side of power vent MUST be clear of any obstruction. Such as: 

landscaping plants, landscaping mulch, landscaping timbers etc. 

h. 

DO NOT

 install over wood deck. 

i. 

DO NOT 

install under a deck. 

 

3.  Before starting refer to Typical Installation Configuration Diagram on Page 15. Familiarize yourself with the layout of 

an installation. Determine the vent system termination location (See Diagram A on Page 5) and prepare the 
installation area: When through the wall vent penetration must be near or below the surrounding grade use a SWG-
VR-AF series power vent riser. Provision must be made to protect the vent riser from standing water. A well structure 
must be used with adequate drainage and protection from water runoff. When a well structure is utilized, adequate 
clearance from the well wall to the vent riser 

MUST

 allow for installation, inspection and cleaning of debris.  It is 

recommended that a sill structure and grating be employed to help prevent water and debris entry into the well (See 
Figure 4).  Refer to local building codes governing such structures. 

 

 

Figure 1

 

Содержание SWG-AF Series

Страница 1: ...quirements of the authority having jurisdiction WARNING Read the installation instructions carefully and completely before proceeding with the installation For continued safe operation the appliance v...

Страница 2: ...presentative is engaged in and is responsible for installation and operation of solid or bio fuel heating appliances Who is experienced in such work familiar with all the precautions required and has...

Страница 3: ...to air flow fluctuations during operation Fluctuations occur from wind loads on the outlet of the power vent house de pressurization and ventilation requirements use a Field Controls Type M or RC Bar...

Страница 4: ...to installation location Diagram A Page 5 for typical locations a The exit termination of mechanical draft systems shall not be less than 7 above grade when located adjacent to public walkways b A ven...

Страница 5: ...unit mounts directly on the wall board to provide a stable support Note When the siding is greater than 1 2 thick use a spacer plate or board behind the power vent mounting base See Figure 2 5a SWG A...

Страница 6: ...iece Backing Plate Installation a Position Upper Backing Plate Half on the inside wall Place plate half on inside wall and up to the vent body At the same time Put the air pressure sensing tube throug...

Страница 7: ...ical Code and or International Residential Code and local codes for guidance Installation within Canada must be with accordance to the latest version of CSA B 365 Installation Code for Solid Fuel Burn...

Страница 8: ...draft control into collar The front face of the control must be plumb The pivot points must be level whether the control is on a horizontal vertical or sloping flue pipe Use a spirit level plumb and l...

Страница 9: ...s located Turn on clothes dryers any exhaust fans such as range hoods and bathroom exhausts so they operate at maximum speed Do not operate a summer exhaust fan If after completing Steps 3 through 7 i...

Страница 10: ...Page 10 WIRING DIAGRAM...

Страница 11: ...ntains the Motor and Blower Wheel It is factory assembled to a mounting bracket MODEL REPAIR MOTOR KIT SWG 4AF 46544400 SWG 5AF 46544500 SWG 6AF 46544600 REMOVAL AND INSTALLATION OF THE SWG AF SERIES...

Страница 12: ...y maintain the appliance switch combination can lead to Death Personal Injury and or Property Damage INSTALLATION MOUNTING IN THE VENT PIPE 1 Drill or pierce a clean hole 3 4 1 32 diameter in the vent...

Страница 13: ...local codes WMO 1 SWITCH MAINTENANCE Note For continued safe operation the appliance switch combination is required to be inspected and maintained annually by a qualified agency 1 Disconnect power to...

Страница 14: ...after the appliance has operated a sufficient time to establish stable combustion adjust pressure switch sensitivity by turning pressure switch adjustment screw clockwise See Figure 19 until burner f...

Страница 15: ...Page 15 TYPICAL INSTALLATION CONFIGURATION...

Страница 16: ...ystem as a guide for tune up or service information annually DATE EQUIPMENT SETUP INFORMATION Heating Appliance BTU HR Input Vent System Draft Before Barometric Draft Control Vent System Draft After B...

Страница 17: ...Page 17...

Страница 18: ...t identifying the Product purchased Product model or accurate date code information and the date the Product s was purchased 3 Product whose warranty quality stickers Product serial numbers plates or...

Страница 19: ...ctions de pose avec attention et en entier avant de proc der la pose Pour assurer un fonctionnement sans danger l ensemble appareil de chauffage et syst me d vacuation doit tre contr l et entretenu ch...

Страница 20: ...e type de travaux est familiaris e avec les pr cautions de rigueur et est en r gle vis vis des autorit s comp tentes L installateur doit crire ou imprimer son nom son num ro de t l phone et la date d...

Страница 21: ...e blocage d vacuation WMO 1 doivent IMP RATIVEMENT tre correctement install s et assurer un verrouillage appropri du circuit d alimentation du br leur de l appareil Table 1 TABLEAU DE DIMENSIONS DE L...

Страница 22: ...ssus du niveau du sol lorsqu elle est contigu des voies pi tonnes publiques b Un syst me d vacuation doit se terminer au moins 0 9 m 3 pi au dessus de toute prise d air forc e plac e moins de 3 m 10 p...

Страница 23: ...nlev pour les poses travers des murs en mat riaux non combustibles Il peut tre n cessaire de couper le manchon d embo tement mural la longueur pour les paisseurs de mur de moins de 20 cm 8 po 5b S RIE...

Страница 24: ...ement derri re le plateau de fixation de l vacuation forc e voir Figure 5 Pose de la plaque de fixation en deux pi ces a Placer la demi plaque de fixation sup rieure sur l int rieur du mur Poser la de...

Страница 25: ...Code d installation des appareils combustibles solides et du mat riel connexe Si un conduit d vacuation pr fabriqu double paroi est requis ou utilis pour l installation le d gagement doit tre bas sur...

Страница 26: ...b Les points de pivotement doivent tre de niveau que le r gulateur soit pos sur un tuyau de fum e horizontal vertical ou inclin l aide d un niveau bulle v rifier l aplomb et le niveau avec pr cision A...

Страница 27: ...ouve l appareil Faire fonctionner tous les s che linge ventilateurs d extraction tels que hottes de cuisine et ventilateurs aspirants de salle de bain leur vitesse maximale Ne pas faire fonctionner de...

Страница 28: ...ffage Se reporter aux instructions de pose de l appareil Contacteur de blocage d vacuation WMO 1 Contacteur de contr le de tirage DIP 1 Connecteur de tube de dia ext po jusqu 15 m 50 pi de l vacuation...

Страница 29: ...CHANGE Si l ensemble moteur turbine doit tre chang les articles suivants sont disponibles Le n cessaire de r paration de moteur SWG AF comprend le moteur et la turbine Il est mont sur un support de fi...

Страница 30: ...mauvais entretien de l ensemble appareil commutateur pr sente un danger de mort de blessures corporelles et de d g ts mat riels POSE POSE DANS LE CONDUIT D EVACUATION 1 Percer ou forer orifice propre...

Страница 31: ...s tout le c blage doit tre en conformit avec le National Electrical Code et les codes locaux en vigueur ENTRETIEN DU COMMUTATEUR WMO 1 Remarque Pour assurer un fonctionnement sans danger l ensemble ap...

Страница 32: ...jusqu ce que l alimentation du br leur s arr te Tourner ensuite la vis de r glage dans le sens inverse jusqu ce que l alimentation du br leur se remette en marche Tourner la vis de r glage de de tour...

Страница 33: ...ES DE PLANCHER AVEC DES COLLIERS POUR TUBE OU QUIVALENT MUR LE CLAPET DE R GULATION DE TIRAGE BAROM TRIQUE DOIT TRE POS D APLOMB VERTICALEMENT ET DE NIVEAU HORIZONTALEMENT ATTENTION FIXER LE TUBE L CA...

Страница 34: ...pour les r glages ou la maintenance annuels DATE DONN ES INITIALES DU MAT RIEL Puissance de l appareil de chauffage en BTU h Tirage du syst me d vacuation avant le r gulateur barom trique Tirage du sy...

Страница 35: ...Page 17...

Страница 36: ...ocollants de garantie qualit les plaques de num ro de s rie du Produit ou les num ros de s rie lectroniques ont t enlev s alt r s ou rendus illisibles n est pas couvert aux termes de la garantie limit...

Отзывы: