Flood Alarm Set - Relay 1 (Parameter Number 31, Parameter Size 1) This defines the behavior of relay 1 in
case of flood alarms
Value
Description
0
Deactivated, devices does not react to alarms
1
Disable on Alarm - will switch off in case of alarm
2
Enable on Alarm - will switch on in case of alarm (Default)
3
Flashing on Alarm - will switch on and off periodically for 10 minutes
Smoke Alarm Set - Relay 1 (Parameter Number 32, Parameter Size 1) This defines the behavior of relay 1
in case of smoke alarms
Value
Description
0
Deactivated, devices does not react to alarms
1
Disable on Alarm - will switch off in case of alarm
2
Enable on Alarm - will switch on in case of alarm
3
Flashing on Alarm - will switch on and off periodically for 10 minutes (Default)
Temperature Alarm Set - Relay 1 (Parameter Number 33, Parameter Size 1) This defines the behavior of
relay 1 in case of temperature alarms
Value
Description
0
Deactivated, devices does not react to alarms
1
Disable on Alarm - will switch off in case of alarm (Default)
2
Enable on Alarm - will switch on in case of alarm
3
Flashing on Alarm - will switch on and off periodically for 10 minutes
Time of Active Alarm (Parameter Number 39, Parameter Size 2) Defines how long a alarm shall be active
Value
Description
0 — 20000 Seconds (Default 600)