ADVAnCED PARAMETERS
53. Energy reports
Energy level change which will result in sending a new energy report.
Available settings:
0
- energy reports disabled
1-255
(0.01-2.55 kWh) - report triggering threshold
Default setting:
10
(0.1 kWh) Parameter size:
2
[bytes]
54. Self-measurement
The Dimmer 2 may include active power and energy consumed by
itself in reports sent to the main controller.
Available settings:
0
- Self-measurement inactive
1
- Self-measurement active
Default setting:
0
Parameter size:
1
[byte]
58. Method of calculating the active power
This parameter defines how to calculate active power. It is useful in a
case of 2-wire connection with light sources other than resistive.
Available settings:
0
- measurement based on the standard algorithm
1
- approximation based on the calibration data
2
- approximation based on the control angle
Default setting:
0
Parameter size:
1
[byte]
59. Approximated power at the maximum brightness level
This parameter determines the approximate value of the power that
will be reported by the device at its maximum brightness level.
Available settings:
0-500
(0-500W) - power consumed by the load
at the maximum brightness level.
Default setting:
0
Parameter size:
2
[bytes]
NOTE
Parameter 58 is set
to 0 after forced au-
to-calibration.
i
NOTE
Parameter 59 works
only when parameter
58 has a value other
than 0.
i