31
ADVAnCED PARAMETERS
46. LOAD ERROR alarm report
(no load, load failure, burnt out bulb)
Available settings:
0
- no reaction
1
- Send an alarm frame
Default setting:
1
Parameter size:
1
[byte]
47. OVERCURRENT alarm report
(short circuit, burnt out bulb caus-
ing overcurrent)
Available settings:
0
- no reaction
1
- Send an alarm frame
Default setting:
1
Parameter size:
1
[byte]
48. SURGE alarm report
(Dimmer 2 output overvoltage)
Available settings:
0
- no reaction
1
- Send an alarm frame
Default setting:
1
Parameter size:
1
[byte]
49.
OVERHEAT
(critical temperature)
and VOLTAGE DROP
(low volt-
age)
alarm report
Available settings:
0
- no reaction
1
- Send an alarm frame
Default setting:
1
Parameter size:
1
[byte]
GROUP 50 - Active power and energy reports
50.
Active power reports
The parameter defines the power level change that will result in a new
power report being sent. The value is a percentage of the previous report.
Available settings:
0
- power reports disabled
1-100
(1-100%) - power report threshold
Default setting:
10
(10%)
Parameter size:
1
[byte]
52. Periodic active power and energy reports
Parameter 52 defines a time period between consecutive reports.
Timer is reset and counted from zero after each report.
Available settings:
0
- periodic reports disabled
1-32767
(1-32767 seconds)
Default setting:
3600
(3600s) Parameter size:
2
[bytes]