48
1.6 network
Setpoints > network > Data link - SCaDa
Setpoint name
Min
Value
Max Value
Units
Description
SCADA Data Link Baud Rate
2400
57600
N/A
SCADA Data Link Parity
N/A
N/A
N/A
Select “None” “Odd” or “Even”
SCADA Data Link Slave Address
1
247
N/A
SCADA Data Link Access Password
0.0
0xfffff
N/A
SCADA Data Link Connection Timeout Interval
0.1
3600.0
sec.
RS-485 Bias Resistor Enable Status
Disabled
Enabled
N/A
1.7 reduced Power Mode
Setpoints > reduced PoWer Mode > Delay Time
Setpoint name
Min
Value
Max
Value
Units
Description
Reduced power mode delay time
1
100
min
The control will run at reduced power mode
after delay. This mode can be disabled using
Level 3 password.