43
1.2 Control
1.2.1 automatic Start/Stop
Setpoints > Control > automatic Start/Stop
Setpoint name
Min
Value
Max
Value
Units
Description
Engine start fault protection activation delay
time
0
300
Sec
Time delay to prevent shut down during start up
from low oil pressure etc.
Crank Duration
5
300
Sec
Amount of time the control energizes (cranks) the
starting motor
Crank Cycle Rest Interval
5
300
Sec
Time the control de-energizes the starting motor
between crank cycles
Engine Purge Cycle Time
0
20
Sec
Maximum Number of Crank Cycles
1
20
N/a
Number of crank/rest cycles that the control will
try.
Cooldown Duration
0
30
Min
The time allowing the engine to run after a normal
shutdown is initiated
Start Aid Activation Time
0
240
Sec
Amount of time the control activates start aid
control output. Set to 10 seconds for a EUI with
prelube option.
Crank Alert Activation Time
0
60
Sec
Amount of time the control activates crank alert
output.
Crank Terminate RPM
100
1000
RPM
Engine speed setting used in order to disengage
the starting motor during engine cranking
Engine Fuel Type Configuration
List
Setpoint allows for selection of “Diesel” or “Natural
Gas”
Fuel Shutoff Solenoid Type Configuration
List
Type of fuel system solenoid used on the
generating set. Select “Energized to run” (ETR) or
“Energized to Shut Off” (ETS).
Engine Cooldown Speed
Configuration
List
Select engine speed during cooldown - rated or
idle.
Engine Operating State Input
Configuration
List
Set to “CAN Input” for common engine interface
engines and set to “Hard Wired ”for non-common
engine interface EUI engines and non-EUI engines.
Engine Idle Operation Enable Status
Engine
List
Fuel Priming Feature Enable Status
List
Engine Coolant Temperature Sensor
Configuration
List
Set to “Sensor” for MUI Engines and set to “Data
Link” for EUI Engines.
Engine Oil Pressure Sensor
Configuration
List
Set to “Sensor” for MUI Engines and set to “Data
Link” for EUI Engines.
Low Idle Low Engine Oil Pressure
Warning Event Threshold
34
690
Kpa
Low Idle Low Engine Oil Pressure
Shutdown Event Threshold
34
690
Kpa
Low Engine Oil Pressure Step Speed
400
1800
RPM
When the engine speed below this, the Low Idle
setpoint is used. Set to 800 RPM for engines rated
at 1000 or 1200 RPM. Set to 1200 RPM for engines
rated at 1500 or 1800 RPM.
Emergency Stop Input Active State
Configuration