28
V&Hz Within limits
– The normal operating range is defined as being neither above the high warning or shutdown thresholds,
nor below the low warning or shutdown thresholds. Activated when measured generator voltage and frequency (that is
calculated as a percentage of rated voltage and frequency) are both within the normal operating range. This deactivates when
either the measured generator voltage or the frequency are outside the normal operating range.
2. SySTeM eVenT
EVENT PARAMETER and EVENT TRIGGER condition need to be selected for SYSTEM EVENT. Table 6 is a list of available system
events.
SySTeM eVenT
Pressure
Gen Frequency
Engine Oil Pressure
Gen Real Power
Gas Pressure
Gen Voltage
Temperature
Primary Data Link
Engine Coolant Temperature
SCADA Data Link (PW2.1 Only)
Engine Oil Temperature
Service Interval Expired
Exhaust Temperature
Unexpected Eng S/D
Gen Rear Bearing Temp
Earth Fault
Gen Winding #1 Temp
Earth Leakage
levels
Engine Controller
Engine Coolant Level
Fuel Leak
Engine Oil Level
Air Damper Closed
Fuel Level
Battery Charger Fail
External Tank Fuel Level
Gen Breaker Open
others
Gen Breaker Closed
Any SPN
Custom events
Accessory Data Link (PW2.1 Only)
Digital Input #1 Custom Event
Battery Charging Sys Volt
Digital Input #2 Custom Event
Battery Voltage
Digital Input #3 Custom Event
Emergency Stop Switch
Digital Input #4 Custom Event
Engine in Cooldown
Digital Input #5 Custom Event
Engine Fail to Start
Digital Input #6 Custom Event
Engine Speed
Analog Input #1 Custom Event
Control Not in Auto
Analog Input #2 Custom Event
Gen Current (Amp)
Analog Input #3 Custom Event
Generator Circuit Breaker Closed
Digital Input #5 Custom Event
Generator Circuit Breaker Locked Out
Digital Input #6 Custom Event
Generator Circuit Breaker Failure to Open
AnalogueInput #1 Custom Event
Generator Circuit Breaker Failure to Close
AnalogueInput #2 Custom Event
Utility to Generator Transfer Failure
AnalogueInput #3 Custom Event
table 6
EVENT TRIGGER is used to select the desired condition in order to trigger the event. Table 7 is a list of the available trigger
conditions.
Any Warning
FMI 02 Data Erratic: Intermittent or Incorrect
Any Shutdown
FMI 03 Voltage Above Normal or Shorted to High Source
Any Warning or Shutdown
Low Warning
FMI 04 Voltage Below Normal or Shorted to Low Source
High Warning
FMI 05 Current Below Normal or Open Circuit
High / Low Warning
FMI 06 Current Above Normal or Grounded Circuit
Low Shutdown
FMI 07 Mechanical System Not Responding or Out of
Adjustment
High Shutdown
FMI 08 Abnormal Frequency: Pulse Width or Period
High / Low Shutdown
FMI 09 Abnormal Update Rate
Low Warning or Shutdown
FMI 10 Abnormal Rate of Change
High Warning or Shutdown
FMI 11 Root Cause Not Known
High / Low Warning or High / Low Shutdown
FMI 12 Bad Intelligent Device or Component
High / Low Warning or High / Low Shutdown or Diagnostic
FMI 13 Out of Calibration
Any Diagnostic
Condition Exists
FMI 14 Special Instruction
Table 7