Festo — SFAB-...-PNLK — 2022-08
IO-Link interface description
31
Index
Sub Index Access
1)
Name
Value
Format
0x003D
(61)
0x03
R/W
Hysteresis (HY)
SFAB-10: 0 … 5400
SFAB-50: 0 … 2700
SFAB-200: 0 … 10800
SFAB-600: 0 … 3240
SFAB-1000: 0 … 5400
IntegerT32
SSC1.2, flow rate monitoring (OutB)
0x003E
(62)
0x00
R/W
SSC1.2Param
Combined value
RecordT
(64 bit)
0x01
Setpoint SP1 (SP,
SP.Lo, SP.Hi)
SFAB-10: 0 … 6000
SFAB-50: 0 … 3000
SFAB-200: 0 … 12000
SFAB-600: 0 … 3600
SFAB-1000: 0 … 6000
IntegerT32
0x02
Setpoint SP2 (SP,
SP.Lo, SP.Hi)
SFAB-10: 0 … 6000
SFAB-50: 0 … 3000
SFAB-200: 0 … 12000
SFAB-600: 0 … 3600
SFAB-1000: 0 … 6000
0x003F
(63)
0x00
R/W
SSC1.2Config
Combined value
RecordT
(48 bit)
0x01
Switchpoint logic
(logic)
0: High-active (nor-
mally open NO)
1: Low-active (normally
close NC)
UInte-
gerT8
0x02
Switchpoint mode
(Fctn)
0: Deactivated
1: Single point mode
(_|¯)
2: Window mode (_|¯|_)
3: Two point mode
(_[]¯)
0x03
Hysteresis (HY)
SFAB-10: 0 … 5400
SFAB-50: 0 … 2700
SFAB-200: 0 … 10800
SFAB-600: 0 … 3240
SFAB-1000: 0 … 5400
IntegerT32
SSC2.1, temperature monitoring
0x400C
(16396)
0x00
R/W
SSC2.1Param
Combined value
RecordT
(64 bit)
0x01
Setpoint SP1
0 … 999
IntegerT32