28
Festo — SFAB-...-PNLK — 2022-08
IO-Link interface description
8.4
IO-Link system commands
Value [dec]
Value [hex]
Command
Description
65
0x41
SP1 Single Value Teach
Determines Teachpoint for Set-
point SP1
66
0x42
SP2 Single Value Teach
Determines Teachpoint for Set-
point SP2
75
0x4B
Specific Teach
Two point teach according to
the teach flag
76
0x4C
Teach Cancel
Cancels the Teach sequence
126
0x7E
Locator Start
Display double flashing for
localization
127
0x7F
Locator Stop
Stop double flashing
128
0x80
Device reset
Device warm start
129
0x81
Application Reset
Reset the technology specific
application
130
0x82
Restore factory settings
Sets the factory settings opera-
tive again
131
0x83
Back-to-box
Restore parameters to the orig-
inal delivery values
160
0xA0
Reset Min MDC1 (q)
Minimal measured flow value
reset
161
0xA1
Reset Max MDC1 (q)
Maximal measured flow value
reset
166
0xA6
Reset Min MDC2 (t)
Minimal measured temperature
value reset
167
0xA7
Reset Max MDC2 (t)
Maximal measured temperature
value reset
168
0xA8
Adjust flow zero point
User defined flow zero point
adjustment
176
0xB0
Reset volume / mass recorder
177
0xB1
Run / resume volume / mass
recorder
178
0xB2
Pause volume / mass recorder
Tab. 16: IO-Link system commands