Festo — SFAB-...-PNLK — 2022-08
IO-Link interface description
25
8
IO-Link interface description
8.1
General information, IO-Link
Feature
Specification
Protocol
IO-Link
Revision ID
V1.1
Device profiles
Smart Sensor - SSP 4.1.2
Firmware Update
identification and diagnosis
Function Measurement data, standard resolution
Function Multiple switching signal
Function Teach single value
Function Extended identification
Function Locator
Function Product URI
Transmission rate
COM3
SIO-Mode support
Yes
Port type
class A
Process data output length
0 bit
Process data input length
64 bit
Process data content IN
Flow measurement value 16 bit MDC
Flow monitoring 2 bit SSC
Temperature measurement value 16 bit MDC
Temperature monitoring 2 bit SSC
Volume / mass pulse 1 bit SSC
Service data IN
Volume /mass measurement value 32 bit
Min. cycle time
1,2 ms
Data storage required
0,5 kByte
Device ID
Tab. 11: General IO-Link specification
Device ID [dec]
Device ID [hex]
Order code
329417
0x0506C9
SFAB-10
329418
0x0506CA
SFAB-50
329419
0x0506CB
SFAB-200