30
Festo — SFAB-...-PNLK — 2022-08
IO-Link interface description
Index
Sub Index Access
1)
Name
Value
Format
0x003B
(59)
0x00
R
Teach Result
0: Combined value
RecordT
(8 bit)
0x01
Teach State
0: Idle, default
1: SP1 Success
2: SP2 Success
3: SP12 Success
4: Wait for command
5: Busy
7: Error
UInte-
gerT4
(4 bit)
0x02
teach flag TP1 for SP1
0: not set
1: set
BooleanT
(1 bit)
0x03
teach flag TP2 for SP1
0x04
teach flag TP1 for SP2
0x05
teach flagTP2 for SP2
SSC1.1, flow rate monitoring (OutA)
0x003C
(60)
0x00
R/W
SSC1.1Param
Combined value
RecordT
(64 bit)
0x01
Setpoint SP1 (SP,
SP.Lo, SP.Hi)
SFAB-10: 0 … 6000
SFAB-50: 0 … 3000
SFAB-200: 0 … 12000
SFAB-600: 0 … 3600
SFAB-1000: 0 … 6000
IntegerT32
0x02
Setpoint SP2 (SP,
SP.Lo, SP.Hi)
SFAB-10: 0 … 6000
SFAB-50: 0 … 3000
SFAB-200: 0 … 12000
SFAB-600: 0 … 3600
SFAB-1000: 0 … 6000
0x003D
(61)
0x00
R/W
SSC1.1Config
Combined value
RecordT
(48 bit)
0x01
Switchpoint logic
(logic)
0: High-active (nor-
mally open NO)
1: Low-active (normally
close NC)
UInte-
gerT8
0x02
Switchpoint mode
(Fctn)
0: Deactivated
1: Single point mode
(_|¯)
2: Window mode (_|¯|_)
3: Two point mode
(_[]¯)