Festo — SFAB-...-PNLK — 2022-08
IO-Link interface description
35
Index
Sub Index Access
1)
Name
Value
Format
0x017F
(383)
0x00
R/W
flow unit of the dis-
play(q, FLOW/Unit)
0: l/min
2: m
3
/h
3: scfm
4: g/min
UInte-
gerT16
0x0181
(385)
0x00
Flow display filter
MDC1 (q, AVER)
8: 256 ms
9: 512 ms
10: 1024 ms
0x0182
(386)
0x00
Flow filter response
time MDC1 (q, Filt)
0: Filter off
1: 2 ms
2: 4 ms
3: 8 ms
4: 16 ms
5: 32 ms
6: 64 ms
7: 128 ms
8: 256 ms
9: 512 ms
10: 1024 ms
11: 2048 ms
0x0184
(388)
0x00
User zero adjustment
on/off (Z.Adj)
0: off
1: on
0x01A7
(423)
0x00
R
Volume / mass unit
0: l
1: m
3
2: scf
3: g
0x01BB
(443)
0x00
R/W
Temperature unit MDC2
(t, tEMP/Unit)
0: °C
1: °F
0x01DC
(476)
0x00
Show local SSCs in
RUN mode on the dis-
play
0: Only active SSCs
1: All local SSCs
0x01DD
(477)
0x00
Measured value display 0: flow
1: Volume / mass pulse
2: temperature
0x01E1
(481)
0x00
Digital output hardware
mode (Out/bin)
0: NPN
1: PNP