Make sure that the fastening surface can
carry this weight.
•
Fit a hat rail (support rail EN 50022 - 35x15;
width 35 mm, height 15 mm).
•
Fasten the hat rail to the mounting surface at
least every 100 mm.
•
Hang the terminal onto the hat rail. Secure
the terminal on both sides against tilting or
slipping with the hat rail clamping unit (see
diagram below).
•
If the terminal is fitted in a sloping position or
at a point subjected to vibration, use two
screws (7) to protect the hat rail clamping unit
against unintentional loosening/opening.
Hat rail clamping unit
locked
Retaining screw (7)
Valve terminal
type 03
Fig. 2/5: Fitting the valve terminal type 03 onto a hat rail
VIFB16 - 03/05
2. Fitting
0506b
2-11
Содержание FB16
Страница 2: ...VIFB16 03 05...
Страница 4: ...Order no 164222 Title MANUAL Designation P BE VIFB16 03 05 GB VIFB16 03 05 II 0506b...
Страница 17: ...1 SYSTEM SUMMARY VIFB16 03 05 1 User instructions 0506b 1 1...
Страница 29: ...2 FITTING VIFB16 03 05 2 Fitting 0506b 2 1...
Страница 42: ...VIFB16 03 05 2 Fitting 2 14 0506b...
Страница 43: ...3 INSTALLATION VIFB16 03 05 3 Installation 0506b 3 1...
Страница 82: ...VIFB16 03 05 3 Installation 3 40 0506b...
Страница 83: ...4 COMMISSIONING VIFB16 03 05 4 Commissioning 0506b 4 1...
Страница 138: ...VIFB16 03 05 4 Commissioning 4 56 0506b...
Страница 139: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB16 03 05 5 Diagnosis error treatement 0506b 5 1...
Страница 165: ...TECHNICAL APPENDIX VIFB16 03 05 Appendix A 0506b A 1...
Страница 183: ...INDEX VIFB16 03 05 Index 0506b B 1...
Страница 184: ...VIFB16 03 05 Index B 2 0506b...
Страница 190: ...VIFB16 03 05 Index B 8 0506b...