The possible errors are grouped into the follo-
wing three categories in the ORPHEE software:
Error
category
General meaning
Valve terminal diagnosis
Internal
errors
Internal errors concern the
general function of a hardware
module or the FIPIO slave.
Not relevant
External
errors
External errors are device-
specific errors which are
registered by the FIPIO field bus
slave.
Error entries of the valve
terminal:
EF1 = External error 1 = V
out
*)
EF2 = External error 2 = V
val
*)
EF3 = External error 3 = V
sen
*)
EF4 = External error 4 = Sh.
c./o.
*)
Logical
errors
Logical errrors refer to
parametrizing errors.
Not relevant
The error messages of internal and logical errors are identical with all
devices/field bus slaves. The valve terminals create device-specific messages
only with external errors.
Fig. 5/14b: Structure of the error categories of the ORPHEE software
*)
The diagnostic information of the valve
terminal has the following meaning:
Diagnostic
information
Meaning
Cause
Short
circuit/
overload
Monitors the electrical outputs
of the output modules.
Short circuit
or
overload
V
sensors
(V
sen
)
Monitors the supply voltage of
the inputs (sensors).
Internal fuse triggered
V
outputs
(V
out
)
Monitors the operating voltage
of the valves and electrical
outputs (no voltage available
e.g. EMERGENCY STOP).
Operating voltage at pin 2 of
operating voltage connection
< 10 V
V
valves
(V
val
)
Monitors the tolerance of the
operating voltage of the valves
and electrical outputs.
Operating voltage at pin 2 of
operating voltage connection
< 21.6 V
Fig. 5/14c: Error states of valve terminal
VIFB16 - 03/05
5. Diagnosis/error treatment
5-22
0506b
Содержание FB16
Страница 2: ...VIFB16 03 05...
Страница 4: ...Order no 164222 Title MANUAL Designation P BE VIFB16 03 05 GB VIFB16 03 05 II 0506b...
Страница 17: ...1 SYSTEM SUMMARY VIFB16 03 05 1 User instructions 0506b 1 1...
Страница 29: ...2 FITTING VIFB16 03 05 2 Fitting 0506b 2 1...
Страница 42: ...VIFB16 03 05 2 Fitting 2 14 0506b...
Страница 43: ...3 INSTALLATION VIFB16 03 05 3 Installation 0506b 3 1...
Страница 82: ...VIFB16 03 05 3 Installation 3 40 0506b...
Страница 83: ...4 COMMISSIONING VIFB16 03 05 4 Commissioning 0506b 4 1...
Страница 138: ...VIFB16 03 05 4 Commissioning 4 56 0506b...
Страница 139: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB16 03 05 5 Diagnosis error treatement 0506b 5 1...
Страница 165: ...TECHNICAL APPENDIX VIFB16 03 05 Appendix A 0506b A 1...
Страница 183: ...INDEX VIFB16 03 05 Index 0506b B 1...
Страница 184: ...VIFB16 03 05 Index B 2 0506b...
Страница 190: ...VIFB16 03 05 Index B 8 0506b...