AP parameter
ID
Parameter
Instance-
s
Data
type
Access
1)
Arraysize
246
Fieldbus serial number
1
UINT32
ro
–
791
Product key
1
CHAR
ro
12
960
Firmware version
1
CHAR
ro
40
20000
Module code
1
UINT32
ro
–
20085
Measured value temperature AP-ASIC [°C]
1
INT16
ro
–
20087
Current measured value of logic supply PS
[mV]
1
UINT16
ro
–
20088
Current measured value of load supply PL
[mV]
1
UINT16
ro
–
20093
Hardware version
1
UINT8
ro
–
1) ro = read only; rw = read write
Tab. 14 AP parameter
10
Diagnostics and fault clearance
10.1
Diagnostics options
Diagnostics via LED displays
The system and network status and errors are displayed directly on the module via LED indicators
è
Diagnostics via PROFIBUS
Diagnostics as part of the PROFIBUS functions (DPV1) via control software over the network
è
10.4 Diagnostics via PROFIBUS.
10.2
Diagnostic messages
Only the diagnostic messages of the interface are listed in the following table.
Module-specific diagnostic messages
è
Instructions for the applicable module
Information on grouping and displaying the diagnostic messages
è
Instruction manual for the auto-
mation system CPX-AP.
ID hex (dec)
Message
Description
Overvoltage of the logic supply PS 24 V DC was detected.
Remedy
–
Check logic supply PS.
02
|
01
|
0017
(33619991)
Overvoltage in logic
supply PS 24 V DC
Diagnost-
ic status
Error
Diagnostics and fault clearance
12
Festo — CPX-AP-I-PB-M12 — 2020-03
Содержание CPX-AP-I-PB-M12
Страница 1: ...8099778 CPX AP I PB M12 PROFIBUS interface 8099778 2020 03 8099780 Instructions Operat ing...