ID hex (dec)
Message
Description
The system starts.
Remedy
–
0B
|
00
|
0140
(184549696)
System start
Diagnost-
ic status
Information
Firmware invalid
Remedy
–
Repeat transmission of firmware package.
0B
|
04
|
00B7
(184811703)
Firmware invalid
Diagnost-
ic status
Error
The version of the Diagnostic Full Image is not supported.
Remedy
–
Check and adjust firmware versions of
master and devices.
0B
|
08
|
018F
(185074063)
Unsupported Full Dia-
gnostic Image version
Diagnost-
ic status
Error
The diagnostic version is not supported.
Remedy
–
Check and adjust firmware versions of
master and devices.
0B
|
08
|
0190
(185074064)
Unsupported dia-
gnostic version
Diagnost-
ic status
Error
Initialisation of the device failed.
Remedy
–
Check whether additional diagnostic mes-
sages are pending.
–
Reset device to factory settings.
0B
|
07
|
00CC
(185008332)
Initialisation failed
Diagnost-
ic status
Error
The device description file stored in the device at the fact-
ory is invalid or missing.
Remedy
–
Restart device.
–
Check AP system communication.
–
Check firmware version.
–
In the event of repeated errors, contact
Festo Service.
0B
|
09
|
0128
(185139496)
APDD invalid
Diagnost-
ic status
Error
Diagnostics and fault clearance
15
Festo — CPX-AP-I-PB-M12 — 2020-03
Содержание CPX-AP-I-PB-M12
Страница 1: ...8099778 CPX AP I PB M12 PROFIBUS interface 8099778 2020 03 8099780 Instructions Operat ing...