background image

10.4

Diagnostics via PROFIBUS

The automation system CPX-AP supports the following diagnostic options via PROFIBUS DP in accord-
ance with IEC 61158.

DPV1

Station status (standard diagnostics)

Device-related diagnostics (alarm messages)

Identifier-related diagnostics (diagnostics assigned to the modules)

Channel-related diagnostics (diagnostics assigned to the channels)

Module number

Channel number and input/output

Type of diagnostics (error type/channel type)

The diagnostic information is sent to the master system only when the diagnostic mode is activated.

10.4.1

Overview of diagnostic bytes

Station status (6 bytes)

Byte

Contents

Explanation

1

Station status 1

è

 Tab. 23 Station status 1

2

Station status 2

è

 Tab. 24 Station status 2

3

Station status 3

è

 Tab. 25 Station status 3

4

Diag.Master_add

Address of the master after parameterisation (factory setting
255).

5

Ident_number
(high byte)

Manufacturer ID 0x11 (high byte)

6

Ident_number
(low byte)

Manufacturer ID 0x42 (low byte)

Tab. 17 Station status (6 bytes)

Diagnostics and fault clearance

17

Festo — CPX-AP-I-PB-M12 — 2020-03

Содержание CPX-AP-I-PB-M12

Страница 1: ...8099778 CPX AP I PB M12 PROFIBUS interface 8099778 2020 03 8099780 Instructions Operat ing...

Страница 2: ...Translation of the original instructions PI PROFIBUS PROFINET is a registered trademark of its respective trademark holder in certain coun tries 2 Festo CPX AP I PB M12 2020 03...

Страница 3: ...2 Configuration 6 5 2 1 Product design 6 5 2 2 LED displays 7 5 2 3 Control elements 7 5 2 4 Connecting elements 8 6 Assembly 9 7 Installation 9 8 Commissioning 9 9 Parameterisation 10 10 Diagnostics...

Страница 4: ...determined using the product label There may be an updated version of this document for these or later product versions www festo com sp 1 3 Product labelling The product labelling is located on the...

Страница 5: ...g in commercial and residential mixed use areas it may be necessary to take measures to suppress radio interference Use only in combination with modules and components that are permissible for the res...

Страница 6: ...ounting interface connection side top 2 DIL switch cover 3 Network connection PROFIBUS DP OUT 4 Connection for system communication XF21 5 Connection for voltage forwarding XD2 6 Mounting interface co...

Страница 7: ...LED displays 5 2 3 Control elements DIL switches Function The station number of the interface is set in binary code using DIL switches 1 7 Permissible station numbers 1 125 Factory setting 3 Diagnost...

Страница 8: ...V DC logic supply PS 4 24 V DC load supply PL Tab 6 Connection for voltage forwarding Connection for system communication XF20 XF21 Socket M8 4 pin D coded Signal 1 RX Received data 2 TX Transmitted...

Страница 9: ...BUS Use network cables as described in the cable specification 12 Technical data 8 Commissioning 1 Set up an automation project for the higher order controller using suitable software 2 Import the dev...

Страница 10: ...e modules in an automation sys tem CPX AP and adapting the modules to the application situation Fieldbus startup parameters ID Parameter Instance s Data type Access1 Arraysize 20022 Configuration of v...

Страница 11: ...8 with the following meaning Bit 0 degree of severity information 1 Bit 1 degree of severity maintenance 1 Bit 2 degree of severity warning 1 Bit 3 degree of severity error 1 Bit 4 5 reserved Bit 6 mo...

Страница 12: ...rors are displayed directly on the module via LED indicators 10 3 LED displays Diagnostics via PROFIBUS Diagnostics as part of the PROFIBUS functions DPV1 via control software over the network 10 4 Di...

Страница 13: ...ter specified in the AP device descrip tion does not exist in the device or deviates from the spe cification Remedy Check firmware version 06 00 0109 100663561 Startup parameter rejected by device Dia...

Страница 14: ...t ers Restart AP system Check the cable 08 01 0132 134283570 Output process data watchdog of the inter face expired Diagnost ic status Error The process data watchdog for the input data in the inter f...

Страница 15: ...pported Remedy Check and adjust firmware versions of master and devices 0B 08 0190 185074064 Unsupported dia gnostic version Diagnost ic status Error Initialisation of the device failed Remedy Check w...

Страница 16: ...LED displays Bus Error BF LED red Meaning Remedy Station number not correct e g address is assigned twice Check setting of the DIL switches on the interface Bus interface faulty Check bus interface of...

Страница 17: ...s error type channel type The diagnostic information is sent to the master system only when the diagnostic mode is activated 10 4 1 Overview of diagnostic bytes Station status 6 bytes Byte Contents Ex...

Страница 18: ...er 8h 26 Module 0 7 27 Module 8 15 32 Module 48 55 1 bit per module to display pending diagnostics Tab 19 Identification related diagnostics 9 bytes Channel related diagnostics 3 bytes A maximum of 9...

Страница 19: ...0 2 Slot number module x 0 1 0 1 0 1 0 1 0 1 0 1 0 1 No further differentiation 0 0 Error coming slot is not OK 0 1 Error going slot is OK 1 0 An error is pending slot is not OK 1 1 Slave does not req...

Страница 20: ...NCE REQUIRED 4 WARNING 8 ERROR 12 13 AP slot from data type UINT16 14 15 AP sub slot from data type UINT16 16 17 AP channel from data type UINT16 18 AP type 0 UNUSED 1 SYSTEM 2 MODULE 3 SUBMODULE 4 CH...

Страница 21: ...ter do not agree with the configuration determined by the auto mation system CPX AP 3 Diag Ext_Diag A diagnostics message is pending Possible causes Cable break at input output module Short circuit ov...

Страница 22: ...e_Mode The Freeze control command is activated 5 Diag Sync_Mode The Sync control command is activated 6 Reserved 7 Diag Deactivated always 0 fixed by the automation system CPX AP Tab 24 Station status...

Страница 23: ...he module related diagnostic block including the header byte 9 bytes 0 0 1 0 0 0 25 Bit 7 and bit 6 are permanently assigned 0 1 Pending diagnostics at Module 0 1 Module 1 1 Module 2 1 Module 3 1 Modu...

Страница 24: ...nd channel orientated faults on a module only the module ori entated diagnostic message will be entered If there are several channel orientated faults on a module only the diagnostic message of the ch...

Страница 25: ...f diagnostics error type channel type Value Error type standard Value Error type Festo 0 Reserved 16 Parameter set invalid 1 Short circuit 17 Value outside the range 2 Undervoltage 18 Switch off of th...

Страница 26: ...dity non condensing 5 95 Assigned address space inputs outputs Bytes 1024 1024 max Module code hex dec 0x2082 8322d Module identification CPX AP I PB M12 Degree of protection in accordance with EN 605...

Страница 27: ...pply PS ms 10 Load supply PL V DC 24 25 Intrinsic current con sumption at nominal voltage 24 V from PL mA Typ 3 Reverse polarity pro tection 24 V PL against 0 V PL Yes Diagnostic message undervoltage...

Страница 28: ...500 kbps 400 max at 500 kbps 1000 max at 187 5 kbps 1200 max at 9 6 93 75 kbps Stub line length dependent on transmission speed 1500 kbps m 6 6 1500 kbps m No branch lines permitted Cable specificatio...

Страница 29: ......

Страница 30: ...2020 all rights reserved to Festo SE Co KG Copyright Festo SE Co KG 73734 Esslingen Ruiter Stra e 82 Germany 49 711 347 0 www festo com Internet Phone...

Отзывы: