ID hex (dec)
Message
Description
The communication to the AP Master is aborted.
Remedy
–
Restart AP Master.
–
Check communication cable (AP).
08
|
01
|
0124
(134283556)
AP Master lost
Diagnost-
ic status
Error
The AP system communication to a module is aborted.
Remedy
–
Restart AP system.
–
Check the cable.
08
|
01
|
0127
(134283559)
Communication to AP
module interrupted
Diagnost-
ic status
Error
The process data watchdog for the output data in the
interface has expired.
Remedy
–
Match cycle time and watchdog paramet-
ers.
–
Restart AP system.
–
Check the cable.
08
|
01
|
0132
(134283570)
Output process data
watchdog of the inter-
face expired
Diagnost-
ic status
Error
The process data watchdog for the input data in the inter-
face has expired.
Remedy
–
Match cycle time and watchdog paramet-
ers.
–
Restart AP system.
–
Check the cable.
08
|
01
|
0133
(134283571)
Input process data
watchdog of the inter-
face expired
Diagnost-
ic status
Error
A module has not mirrored the toggle bit in the process
data.
Remedy
–
Match cycle time and toggle timeout para-
meters.
–
Restart AP system.
–
Check the cable.
08
|
01
|
0134
(134283572)
AP Master Toggle bit
error
Diagnost-
ic status
Error