ID hex (dec)
Message
Description
Undervoltage in the load supply PL 24 V DC was detected.
Remedy
–
Check load supply PL.
02
|
01
|
0105
(33620229)
Undervoltage in load
supply PL 24 V DC
Diagnost-
ic status
Error
A switch-off of the load supply PL was detected. The cause
can be a deliberate shutdown by the emergency stop.
Remedy
–
Check if the emergency stop was activ-
ated.
–
Check load supply PL.
02
|
01
|
0106
(33620230)
Switch-off load supply
PL 24 V DC
Diagnost-
ic status
Information
Overvoltage load supply PL 24 V DC
Remedy
–
Check load supply PL.
02
|
01
|
013F
(33620287)
Overvoltage load sup-
ply PL 24 V DC
Diagnost-
ic status
Error
The startup parameter specified in the AP device descrip-
tion does not exist in the device or deviates from the spe-
cification.
Remedy
–
Check firmware version.
06
|
00
|
0109
(100663561)
Startup parameter
rejected by device
Diagnost-
ic status
Error
The length of the start-up parameter in the device differs
from the specified length in the AP device description.
Remedy
–
Check firmware version.
06
|
00
|
010A
(100663562)
Start-up parameter
deviation in length
Diagnost-
ic status
Error
Transferred device address is invalid.
Remedy
–
Check address configuration. Is the con-
figuration set via software or hardware
(DIL switch)?
–
Check the assigned address for the
device.
–
Check multiple address assignment.
–
Check the DIL-switch setting.
08
|
00
|
012E
(134218030)
Device address
invalid
Diagnost-
ic status
Warning
Diagnostics and fault clearance
13
Festo — CPX-AP-I-PB-M12 — 2020-03