Diagnostics alarm (byte 5 … 22)
Byte
Contents
Value
5
AP diagnostics version
from data type UINT8
6
…
9
AP diagnostics ID
from data type UINT32
10
AP notification type
0: INFORM
1: RAISE
2: RESOLVE
3: WAIT_FOR_ACKNOWLEDGE
4: ACKNOWLEDGE
5: COLLECTIVE ACKNOWLEDGE
6: STATUS_CHANGE
7: REFRESH_NOTIFICATION
8: REFRESH_REQUEST
9: REFRESH_START
10: REFRESH_END
11
AP priority/importance of the
message
1: INFORMATION
2: MAINTENANCE REQUIRED
4: WARNING
8: ERROR
12
…
13 AP slot
from data type UINT16
14
…
15 AP sub-slot
from data type UINT16
16
…
17 AP channel
from data type UINT16
18
AP type
0: UNUSED
1: SYSTEM
2: MODULE
3: SUBMODULE
4: CHANNEL_IN
5: CHANNEL_OUT
6: CHANNEL_INOUT
19
Reserved
–
20
AP slot status
(AP diagnostics status)
21
AP sub-slot status
(AP diagnostics status)
22
AP channel status
(AP diagnostics status)
Bit 0 = 1: Information
Bit 1 = 1: Maintenance
Bit 2 = 1: Warning
Bit 3 = 1: Error
Bit 7 = 1: severity has changed
Bits 4, 5 and 6 are reserved.
Tab. 22 Diagnostics alarm (byte 5... 22)
Diagnostics and fault clearance
20
Festo — CPX-AP-I-PB-M12 — 2020-03
Содержание CPX-AP-I-PB-M12
Страница 1: ...8099778 CPX AP I PB M12 PROFIBUS interface 8099778 2020 03 8099780 Instructions Operat ing...
Страница 29: ......