Mounting and installation
26
Festo – GDCP-CMCA-INST-EN – 1211a – English
4.2.2
Design of the double-stack terminals
The double-stack terminals of the terminal strips X2 … X6 and the right part of X1 have the following
design.
Connection number with the labelling on top
The terminals on top correspond to the terminal
numbers also attached somewhat further on top
(here 610 … 618).
Both connections of a terminal are bridged intern-
ally.
Fig. 4.4
Connection number with the labelling underneath
The terminals below correspond to the terminal
numbers also attached somewhat further under-
neath (here 600 … 608).
Both connections of a terminal are bridged intern-
ally.
Fig. 4.5
4.2.3
Connecting supply voltage
Note
In the control cabinet design, guide the supply lines of the supply voltage through the
left one of the two cut-outs on the bottom of the control cabinet.
Guide the supply line of the supply voltage (230/400 V AC / 3-phase, 50 … 60 Hz) in the cable duct to
the terminal strip X0. Attach the conductors to the lower clamping contacts of the terminals.