QUADRIFOGLIO
53
EN
Key
- Parameters
Each system requires a different parameterisation. Follow the access procedure given
below.
“Service Menu”
The card Service Menu is accessed by pressing the Reset button for 10 seconds.
Press the Heating buttons to select “tS”, “In”, “Hi” or “rE”
“tS”
means Transparent Parameters Menu,
“In”
means Information Menu,
“Hi”
means
History Menu,
“rE”
means History Menu Reset.
Select “tS” and press the Reset button.
Check/Change parameter
P02
of the “Transparent Parameters Menu” to
5
.
Check/Change parameter
P27
of the “Transparent Parameters Menu” to
1
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. To modify the value of a parameter just press the DHW buttons; the change will be
automatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit the card Service Menu.
“System Type Menu”
Press the Summer/Winter button for 10 seconds to access the card System Type Menu
Change parameter
P.09
of the “System Type Menu” to
1
.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Summer/Winter button for 10 seconds to exit the card System Type Menu.
- Optional Functions
As well as the electrical connections of the previous figure (required for this system con-
figuration) there are options that do not require settings.
Key
A direct heating circuit and a DHW circuit with diverter valve (3-wire)
- Schematic diagram
Use diverter valves with 3 wires:
- OPENING PHASE 230V
- CLOSING PHASE 230V
- NEUTRAL
with switching times (from all closed to all open) of not more than 90 seconds.
fig. 21
- Electrical connections
After installation, carry out the necessary electrical connections as shown on the wiring
diagram.
Then configure the controller as described in the specific section.
fig. 22
Key
- Parameters
Each system requires a different parameterisation. Follow the access procedure given
below.
“Service Menu”
The card Service Menu is accessed by pressing the Reset button for 10 seconds.
Press the Heating buttons to select “tS”, “In”, “Hi” or “rE”
“tS”
means Transparent Parameters Menu,
“In”
means Information Menu,
“Hi”
means
History Menu,
“rE”
means History Menu Reset.
Select “tS” and press the Reset button.
Check/Change parameter
P02
of the “Transparent Parameters Menu” to
6
.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. To modify the value of a parameter just press the DHW buttons; the change will be
automatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit the card Service Menu.
72
Room thermostat 1st zone (direct)
a
1st zone (direct)
130
Hot water tank circulating pump
b
Hot water tank circuit
138
External probe
M
Delivery
155
Hot water tank probe
RA
High Temperature Return
300
Legionella protection circulating pump
RB
Low Temperature Return
306
Circulating pump 1st zone (direct)
I*
ISPESL safety devices (When required - not supplied)
To manage sliding temperature it is necessary to purchase the external probe accessory code 013018X0
If a hot water tank probe (not supplied) is used, it is necessary to purchase the NTC probe accessory code
1KWMA11W (2 mt.) or code 043005X0 (5 mt.)
If a hot water tank thermostat (not supplied) is used, it is necessary to purchase the kit accessory code
013017X0 (to be connected in place of the Hot Water Tank Probe)
139
Remote Control: it can be installed in place of 72 to manage the request of the 1st zone (direct)
301
Fault indication (voltage-free contact output): the example shows the connection of a lamp at 230Vac
302
Remote reset input (230Vac): the example shows the connection of a double-pole switch at 230Vac, allowing
the resetting of a block type fault
357
Fault indication (230Vac): the example shows the connection of a lamp at 230Vac
5
6
7
8
9 10 11 12
16 17 18 19 20 21 22 23 24 25 26 27
139
FUSIBILE
3.15A
4
13 14 15
28 29 30 31 32 33
301
302
FUSIBILE
Esterno
N
L
L
N
34 35 36
357
32
Heating circulating pump
a
1st zone (direct)
72
Room thermostat 1st zone (direct)
b
Hot water tank circuit
138
External probe
M
Delivery
155
Hot water tank probe
RA
High Temperature Return
306
Circulating pump 1st zone (direct)
RB
Low Temperature Return
348
3-way valve (3-wire)
A =
OPENING PHASE
B =
NEUTRAL
C =
CLOSING PHASE
I*
ISPESL safety devices (When required - not supplied)
To manage sliding temperature it is necessary to purchase the external probe accessory code 013018X0
If a hot water tank probe (not supplied) is used, it is necessary to purchase the NTC probe accessory code
1KWMA11W (2 mt.) or code 043005X0 (5 mt.)
If a hot water tank thermostat (not supplied) is used, it is necessary to purchase the kit accessory code
013017X0 (to be connected in place of the Hot Water Tank Probe)
155
348
32
M
RA
RB
M
I*
b
a
72
138
5
6
7
8
9 10 11 12
16 17 18 19 20 21 22 23 24 25 26 27
72
138
FUSIBILE
3.15A
4
13 14 15
28 29 30 31 32 33
348
32
L
N
L
C B
155
N
A
34 35 36
cod. 3541A282 - Rev. 0
1
- 02/2013