16
Specifications
UltraVoice Indoor Controller (UVIC)
UVIC
Accessories/
Part Numbers
Description
UVIC25ST
Step-down transformer, 70-25 V
rms
(UV25ST with custom cable)
ENWSSPA
Wall-mounted speaker strobe
ENWSTPA
Wall-mounted strobe
ENCSTA
Ceiling-mounted strobe
DSA1
100-watt speaker
Table 3 Ordering UVLOC and UVLOC-IM
UVLOC
Part Numbers
Description
UVLOC
Maximum of (10) units can be interfaced to a UltraVoice Siren
Controller (UV) or UltraVoice Indoor Controller (UVIC)
UVLOC-IM
One (1) Interface module must be ordered per UV or UVIC
Specifications
Specifications for the UVIC
Table 4 Electrical for the UVIC
AC Input Voltage
120 or 240 Vac (UVIC240) +/- 10%
50-60 Hz* Single-phase
(*two separate models)
AC Input Current
5 amps AC
Operating Voltage
24 Vdc
Continuous Signaling Time
30 minutes
Table 5 Battery
Battery Input Voltage
20-28 Vdc, 27 Volts
Battery Current
120 mA standby current, up to 22 A for each amplifier
module running, 50 amps
Battery Capacity
> 45 minutes continuous operation without AC power
Standby Time
> 72 hours (3 days) including two-way radio
(with 5-minute full signal reserve minimum)
Type
VRLA
Rating
44 A/H minimum
Table 6 Environmental
Operating Temperature
-22°F to 149°F/-30°C to +65°C
Humidity
0-98% non-condensing
NOTE
• The UVIC can operate throughout this temperature range provided the battery
temperature is maintained at -18°C/-0.4°F or higher.
• The UVIC housing carries a NEMA 1 rating.