Manual min-pulse calibration of the control loops of the MLS 508:
1)
From the working window switch to the parameter
Manual calibration
via the menu items
Configuration menu
,
Hydraulic calibration
and
Min. pulse calibration
.
2) Call up the parameter
Manual calibration
and follow the instructions displayed.
3)
Pressing the function key F3 completes the min-pulse calibration of the selected
channel. Now perform the min-pulse calibration of all other channels used in the same way.
Then finish the min-pulse calibration and return to the working window or carry out a max-
pulse calibration.