Exiting the programming mode
- Move the mobile jumper J1 from position 2-3 to 1-2. The red LED
flashes slowly (every 2 seconds).
Programming the numerical intervals
To program the numerical intervals:
1) - Move the mobile jumper J1 from position 1-2 to 2-3. The red LED
turns on and stays on.
2) - Select the numerical interval to be programmed by setting jumpers
J2 as shown in table 4.7 and press SW1 to confirm the selection.
- Set jumpers J2 to program numerical interval n.1 (remove jumper
b0 and leave jumpers b1 and b2 – see table 4.7 "Selection of
numerical interval to program on the exchanger") and press SW1;
the LED starts flashing every 2 seconds according to the selected
numerical interval (i.e.: numerical interval n.1 corresponds to 1
flashing every 2 seconds; numerical interval n.2 corresponds to 2
flashings every 2 seconds, etc.).
If line L2 is connected to internal users:
- on the device with the lowest address must:
(myLogic and Zhero series) press
; an intermittent tone is
generated;
(Exhito series) lift the handset and press
key on the
videointercoms or
on the intercoms; replace the handset after
you hear a tone intermittent;
(Echos series) press
; an intermittent tone is generated;
- lift the handset of the device with the highest address and repeat
the previous steps;
- the exchanger red LED turns off for 1 second and starts flashing
again to confirm correct programming;
- repeat the operations above to program the other numerical
intervals, if necessary.
If line L2 is connected to one external door station you must:
- make a call to any user. The exchanger automatically saves the
address of the calling external door station and the external door
station receives the busy line tone;
- the exchanger red LED turns off for 1 second and starts flashing
again to confirm correct programming.
3) - To exit the programming mode, move the jumper J1 from position
2-3 to 1-2. The red LED flashes slowly (every 2 seconds).
Reset default programming
By default the exchanger is not programmed with numbers in the four
numerical intervals.
The four numerical intervals are disabled by default.
To reset default programming:
- move the mobile jumper J1 from position 1-2 to 2-3. The red LED turns
on and stays on;
- insert all jumpers J2;
- hold SW1 pressed for about 4 seconds; the LED flashes rapidly (no
programming is set if the key is released during this time), turns off and
turns on again to confirm correct programming;
- to exit the programming mode, move the jumper J1 from position 2-3
to 1-2. The red LED flashes slowly (every 2 seconds).
Table 4.7
Selection of numerical interval to programme on the exchanger
Jumper J2
b0
b1
b2
numerical interval selection
closed
closed
closed
reset default programming
open
closed
closed
numerical interval n. 1 of L2
closed
open
closed
numerical interval n. 2 of L2
open
open
closed
numerical interval n. 3 of L2
closed
closed
open
numerical interval n. 4 of L2
open
closed
open
not used
closed
open
open
not used
open
open
open
not used
closed = jumper inserted
open = jumper removed
closed
open
confirmation
button
Setting of jumpers J2 and button SW1
SERVICE MODULES
position 2-3
(programming mode)
position 1-2
(operation mode)