FAITHTECH
FTB9000 USER MANUAL
27
item,press
The submenu pops up. As following table:
:
Table 3- 1Settings menu table
Application
Settings
Sampling rate
Sampling transmission rate setting, with 5
optional levels :1000Hz, 500Hz, 200Hz,
100Hz, 10Hz, default 10Hz.
The output is
preferred
Voltage or current is preferred. Default: Volt
(voltage first)
Voltage
Voltage rising slope configuration. The value
ranges from 0.0006V/s to 40,000 V/s. The
default value is 10,000 V/s
Voltage
Voltage drop slope configuration. The value
ranges from 0.0006V/s to 40,000 V/s. The
default value is 10,000 V/s
Source current
Source current rising slope configuration. The
value ranges from 0.0006A/s to 10000A/s.
The default value is 2000A/s
Source current
Source current rising slope configuration. The
value ranges from 0.0006A/s to 10000A/s.
The default value is 2000A/s
Load current
Load current rising slope configuration. The
value ranges from 0.0006A/s to 10000A/s.
The default value is 2000A/s
Load current
Load current down the slope configuration.
The value ranges from 0.0006A/s to
10000A/s. The default value is 2000A/s
Protection
setting
Over
voltage
protection
Set the OVP overvoltage protection point and
set it to 0 to disable the protection
Over
current
protection
Set the OCP overcurrent protection point and
set it to 0 to disable the protection
Power
protection
Set the OPP overpower protection point and
set it to 0 to disable the protection
Under voltage
protection
Set the LVP undervoltage protection point to
0 to disable this protection