21
Control “Dim Up & Dim Down”
This function is automatically available in the selection of “On/Auto” & “Off”. When “On/Auto” is selected, “Dim up” will
automatically function as:
1. Quickly pressing the button switches on the light to the preset level “auto mode”
2. Pressing and holding the button will adjust the light level up, depending on how long the button is held down. It will
continue to dim up for max 5s.
Similar function is available for the “Off” selection:
1. Quickly pressing the button switches the light off completely (Off is equal to scene 7 in this function).
2. Pressing and holding the button adjusts the light level downwards, depending on how long the button held down. It will
continue to dim down for max 5s.
There are three different ways of configuring the communication between wall switch and sensor node in order to suit
most application areas:
1. Zone Pairing
2. Switch ID Pairing
3. Switch ID Pairing One to One
When using Zone Pairing the EnOcean wall switch communicates to all sensor nodes in the zone within radio range, about
10m. The sensor nodes then distributes the message via IR so the remaining nodes in the zone also receives the message.
If no zone is selected, the switch will communicate to all sensor nodes within range regardless of which zones they belong
to. This type of configuration is recommended in all types of installations when a fixed scene is to be sent from the switch
e.g. ON/AUTO, OFF or SCENE 1. If continuous dimming is required in larger zones (≥9 sensor nodes) it’s recommended to
use Switch ID Pairing instead of Zone Pairing.
Note!
It is of most importance that SN3 nodes with FW (firmware) 175 or later are used. Earlier versions of SN3 nodes do not
have this function. Used the Query function to see what version the node has (Note: Only works with iOS devices).
Zone Pairing
Subject to change without notice.
Version5_20200424
Содержание e-Sense Organic G3