15
Subject to change without notice.
Version5_20200424
If necessary, you are able to forward information via a zone, which is not affected. As shown in the image below, pro
-
gramming commands in a corridor (Zone 2) will also affect nodes on the light in the second corridor beyond the office
(also in Zone 2). The function is located under the “Zone” tab and “Forward message for”. Select the zone to be forwarded
(in this case Zone 2) and program it to correspond to a few luminaires in Zone 1. You do not have to program all the lumin-
aires in Zone 1, just a few to ensure the information is correctly relayed. Finish by saving the change. You can also remove
links with the “Ignore” button.
Note: This is only for programming commands, not presence information.
Relay programming information (Forward Message For)
It is also possible to forward information via multiple zones. Use the same procedure to enable the luminaires to relay
information on. It is important to know which zones are used. The reason is that there may be a touch panel located in the
first corridor that will affect Zone 4 in the second corridor.
Relay presence information (Forward Message For) via multiple zones