background image

OPTION 

DESCRIPTION

Active Faults

Information on all active faults

Air Flow

Flow change percentage for all four channels.

Functions

Enter to select, test, isolate, disable, reset 
baseling functions

Event History

View event history

Configuration

View current configuration of the device

LCD Settings

Adjust language setting for LCD, contrast

Message Log

View message log history

Set Time

Set local time on device

Diagnostics

View diagnostics

ACTIVE FAULTS SCREEN

Only the highest priority fault is shown on the home screen, but it is possible 
to for a device to have more than one fault. These faults can be seen with the 
Active Faults screen. The screen displays all active faults from highest to low-
est priority. The priority fault level is as follows:

PRIORITY

FAULT

NOTES

1

Disable

2

Isolate

3

Configuration

5

Sensor

6

Aspirator

7

Internal

Internal HW/Sw failure

8

Low Voltage

9

High Flow ( Ch. 1-4)

10

LowFlow ( Ch. 1- 4)

11

Filter

12

External Monitor

Conventional devices only

13

Time

AIR FLOW SCREEN

The Air Flow screen shows the level of air flow change as a percentage for 
each channel and the programmed boundary level. There is also a bar graph 
to for each channel to provide a visual indication of how close the flow is to 
a boundary level. If not all channels are being used the screen will display 
‘Disabled’ next to the channel.

Air Flow

1

-13%

-2%

-1%

-1%

2

3

4

Enter Password

* * 4 _

ASP111-00

ASP123-00

FIGURE 12. AIR FLOW SCREEN 

FIGURE 13. FUNCTIONS MENU SCREEN 

FUNCTIONS MENU SCREEN

The Functions menu screen is used to change the device’s state or activate 
test mode. Because this menu allows the user to change the device out of its 
normal operating state there is an optional lock out feature for this menu. The 
lockout requires a 4-digit passcode to enter the functions menu – this pass-
code is set using the PipeIQ Software. When the functions menu is accessed 
from the main menu screen with the lock feature enabled, the enter password 
screen will be displayed. 

The scroll (

) keys are used to increment or decrement the number for 

the digit the cursor is on. To enter the number use the select ( 

 ) key and 

the cursor will advance to the next digit. When the last digit is entered the 
Functions menu will be displayed if the password was entered correctly. If 
the password does not match the display will show Password Invalid for 3 
seconds and then return to the home screen.

From the functions menu the following options are available:

•  Isolate

•  Disable

•  Reset

•  Reset Baselines

•  Test

•  Sounder Test

•  Reset IP Network

ISOLATE SCREEN

The Isolate function will set the device into the isolate mode. When this func-
tion is selected from the functions menu the device will display that Isolate 
mode will be activated and will ask for a confirmation. Use the scroll (

keys to select cancel or ok and then select ( 

 ) key to confirm the selection.

DISABLE SCREEN

The Disable function will set the device into the Disable mode. When this 
function is selected from the functions menu the device will ask for confirma-
tion. Use the scroll (

) keys to select cancel or ok and then select ( 

 ) 

key to confirm the selection.

RESET SCREEN

The Reset function will reset the device. When this function is selected from 
the functions menu the device will ask for confirmation. Use the scroll (

keys to select cancel or ok and then select ( 

 ) key to confirm the selection.

RESET BASELINES SCREEN

The Reset Baseline function will set the device into the Reset Baseline mode. 
When this function is selected from the functions menu the device will ask for 
confirmation. Use the scroll (

) keys to select cancel or ok and then select 

 ) key to confirm the selection.

TEST SCREEN

The Test function will set the device into the Test mode. When this function is 
selected from the functions menu the device will ask for confirmation. Use the 
scroll (

) keys to select cancel or ok and then select ( 

 ) key to confirm 

the selection.

 

8 ASUG56601

firealarmresources.com

Содержание XT 9400X

Страница 1: ...ipping Weight 11 8 lb 5 4 kg 1 ASUG56601 TABLE OF CONTENTS Items Included With Unit 2 Connecting to FAAST 9400X 2 Connecting to FAAST via USB 2 Connecting to FAAST via Ethernet 2 Installation 3 Pipe Installation 3 Physical Unit Installation 3 Wiring 4 User Interface 5 Particulate Level Display 5 Alarm Level Display 6 Air Flow Display 6 Fault Display 6 LCD User Interface 7 Configuration Menu Screen...

Страница 2: ...ault conditions Configurable supplementary audible indicator 2 ASUG56601 ITEMS INCLUDED WITH UNIT FAAST 9400X unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable PipeIQ software comprehensive manual and other helpful documents may be downloaded at systemsensor com faast CONNECTING TO FAAST 9400X FAAST 9400X requires a program download from PipeIQ in ord...

Страница 3: ...ropriate conduit caps from the top or bottom left side of the unit to match the orientation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the unit down onto the mounting clips and secure it with the supplied washer and nut on at least one of the two mounting studs protruding through th...

Страница 4: ...e mating connector on the unit FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS ASP114 01 CABLING REQUIREMENTS The FAAST system provides a series of Euro style pluggable terminals located behind the left side door of the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitor ing the FAAST system at a Fire...

Страница 5: ...rovide the device status 6 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring door See the Connecting to FAAST 9400X for detailed connection instructions 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 The PC may now be disconnected ...

Страница 6: ...o the next inlet every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the current air flow is to a high or low fault threshold The default threshold for a fault condition is or 20 from airflow baseline This fault threshold is configu rable using the PipeIQ so...

Страница 7: ...open Minor Fault Time Base Fault Internal Time base needs updating Minor Fault Aspirator Fault Indicates the fan has stopped working and requires immedi ate attention Urgent Fault Filter Fault Device filter is clogged and requires replacement Minor Fault Device filter is clogged and has not been replaced 72 hours af ter giving the Filter Fault with Minor Fault Relay set Urgent Fault Disable Fault ...

Страница 8: ... menu is accessed from the main menu screen with the lock feature enabled the enter password screen will be displayed The scroll keys are used to increment or decrement the number for the digit the cursor is on To enter the number use the select key and the cursor will advance to the next digit When the last digit is entered the Functions menu will be displayed if the password was entered correctl...

Страница 9: ...of the relay and the alarm settings in the device Use the scroll keys to select an option and then select key to confirm the selection RELAYS SETTINGS SCREEN The Relay Settings screen shows the latching setting for each relay A latching relaying will have an X in the box ALARM THRESHOLDS SCREEN The Alarm Thresholds screen shows the five alarm levels To get detailed in formation on an alarm level u...

Страница 10: ... performance of the de vice Therefore when creating a pipe layout the calculations that are per formed are based on the fan setting If the fan setting is changed on the device at a later date the pipe system must be re verified ALARM AND RELAY CONFIGURATION Alarm thresholds are set to default levels when shipped but are configurable Each Alarm level has its own set of form C relay contacts As the ...

Страница 11: ... Level Action 1 Action 1 High Action 1 Low Acclimate Action 1 Level Action 2 Action 2 High Action 2 Low Acclimate Action 2 Level Fire 1 Fire 1 High Fire 1 Low Acclimate Fire 1 Level Fire 2 Fire 2 High Fire 2 Low Acclimate Fire 2 Level DAY NIGHT AND WEEKEND MODE If Acclimate mode is not desired the FAAST system can operate in a simple day night and weekend mode This allows the device to have separa...

Страница 12: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from...

Отзывы: