BUTTON

FUNCTION

Scroll up or down through the LCD menus

Select or enter highlighted item on the LCD screen

Cancel, Back or Escape from current menu selection.

The LCD interface supports multiple languages. LCD language display is set 
using PipeIQ or can be changed by accessing the settings menu in the LCD 
menus. 

HOME SCREEN

The Home screen is the default screen that is initially shown when the LCD is 
activated. The screen will show the device’s current state which includes, local 
address, date, time, current percent of smoke, and the highest priority state. 

If the General Fault LED is illuminated, the fault condition will be shown on 
the LCD display under the Active Faults menu. The possible fault conditions 
are as follows:

TYPE

DESCRIPTION

ACTIVATED RELAY

Low Flow Fault

Device has decrease airflow as 
defined by the user program-
mable boundary.

Minor Fault

Device has decrease airflow 
of 50%

Urgent Fault

Configuration

Configuration of device with 
configuration software has 
failed.

Minor Fault

Device was interrupted with a 
power loss during configura-
tion. A Reset will clear this 
fault and device will revert 
back to it’s last good configu-
ration.

Minor Fault

Device is new and has not 
been configured.

Urgent Fault

Device has corrupt configura-
tion and is unable to operate.

Urgent Fault

Drift Blue Fault

Device blue signal has reached 
the long term drift limit.

Minor Fault

IR Laser Drift Fault Device IR Laser signal has 

reached the long term drift 
limit.

Urgent Fault

Sensor Fault

Device sensor is not work-
ing and requires immediate 
replacement

Urgent Fault

External Monitor 
Fault

External monitor detects open. Minor Fault

Time Base Fault

Internal Time base needs 

 

updating.

Minor Fault

Aspirator Fault

Indicates the fan has stopped 
working and requires immedi-
ate attention.

Urgent Fault

Filter Fault

Device filter is clogged and 
requires replacement

Minor Fault

Device filter is clogged and has 
not been replaced 72 hours af-
ter giving the Filter Fault with 
Minor Fault Relay set

Urgent Fault

Disable Fault

Device has been put in disable 
mode.

Isolation Fault

Isolation Fault

Device has been put in isolate 
mode.

Isolation Fault

High Flow Fault

Device has Increase airflow as 
defined by the user program-
mable boundary.

Minor Fault

Device has decrease airflow 
of 50%

Urgent Fault

Low Voltage Fault

Device Input voltage is low 

Urgent Fault

LCD USER INTERFACE

The FAAST XT has an LCD screen to provide detailed information of the de-
vices status and configuration. The LCD typically will be in an idle state where 
the screen is off. The LCD will enter a sleep state if a single screen has re-
mained unchanged for a period of 30 seconds. A single push of any button 
will wake the screen up and the home screen will be displayed. Once the LCD 
is on, navigation through the menus is done with the buttons on the right 
hand side.

ASP121-00

ASP112-00

FIGURE 10. LCD DISPLAY 

FIGURE 11. HOME SCREEN 

23–JUN-14 10:04AM

System Normal

0.0000 %/ft

Menu

23–JUN-14 10:04AM

System Normal

0.0000 %/ft

Menu

The menu option is available from the home screen. Pressing the select but-
ton will enter the main menu screen. If the device’s sounder is active then the 
only available selection will be Silence. Pressing the select key will silence the 
sounder and then the menu option will appear. 

MAIN MENU SCREEN 

The Main Menu screen shows the options for more detailed information on 
the device. The available options are:

 

7 ASUG56601

firealarmresources.com

Содержание XT 9400X

Страница 1: ...ipping Weight 11 8 lb 5 4 kg 1 ASUG56601 TABLE OF CONTENTS Items Included With Unit 2 Connecting to FAAST 9400X 2 Connecting to FAAST via USB 2 Connecting to FAAST via Ethernet 2 Installation 3 Pipe Installation 3 Physical Unit Installation 3 Wiring 4 User Interface 5 Particulate Level Display 5 Alarm Level Display 6 Air Flow Display 6 Fault Display 6 LCD User Interface 7 Configuration Menu Screen...

Страница 2: ...ault conditions Configurable supplementary audible indicator 2 ASUG56601 ITEMS INCLUDED WITH UNIT FAAST 9400X unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable PipeIQ software comprehensive manual and other helpful documents may be downloaded at systemsensor com faast CONNECTING TO FAAST 9400X FAAST 9400X requires a program download from PipeIQ in ord...

Страница 3: ...ropriate conduit caps from the top or bottom left side of the unit to match the orientation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the unit down onto the mounting clips and secure it with the supplied washer and nut on at least one of the two mounting studs protruding through th...

Страница 4: ...e mating connector on the unit FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS ASP114 01 CABLING REQUIREMENTS The FAAST system provides a series of Euro style pluggable terminals located behind the left side door of the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitor ing the FAAST system at a Fire...

Страница 5: ...rovide the device status 6 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring door See the Connecting to FAAST 9400X for detailed connection instructions 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 The PC may now be disconnected ...

Страница 6: ...o the next inlet every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the current air flow is to a high or low fault threshold The default threshold for a fault condition is or 20 from airflow baseline This fault threshold is configu rable using the PipeIQ so...

Страница 7: ...open Minor Fault Time Base Fault Internal Time base needs updating Minor Fault Aspirator Fault Indicates the fan has stopped working and requires immedi ate attention Urgent Fault Filter Fault Device filter is clogged and requires replacement Minor Fault Device filter is clogged and has not been replaced 72 hours af ter giving the Filter Fault with Minor Fault Relay set Urgent Fault Disable Fault ...

Страница 8: ... menu is accessed from the main menu screen with the lock feature enabled the enter password screen will be displayed The scroll keys are used to increment or decrement the number for the digit the cursor is on To enter the number use the select key and the cursor will advance to the next digit When the last digit is entered the Functions menu will be displayed if the password was entered correctl...

Страница 9: ...of the relay and the alarm settings in the device Use the scroll keys to select an option and then select key to confirm the selection RELAYS SETTINGS SCREEN The Relay Settings screen shows the latching setting for each relay A latching relaying will have an X in the box ALARM THRESHOLDS SCREEN The Alarm Thresholds screen shows the five alarm levels To get detailed in formation on an alarm level u...

Страница 10: ... performance of the de vice Therefore when creating a pipe layout the calculations that are per formed are based on the fan setting If the fan setting is changed on the device at a later date the pipe system must be re verified ALARM AND RELAY CONFIGURATION Alarm thresholds are set to default levels when shipped but are configurable Each Alarm level has its own set of form C relay contacts As the ...

Страница 11: ... Level Action 1 Action 1 High Action 1 Low Acclimate Action 1 Level Action 2 Action 2 High Action 2 Low Acclimate Action 2 Level Fire 1 Fire 1 High Fire 1 Low Acclimate Fire 1 Level Fire 2 Fire 2 High Fire 2 Low Acclimate Fire 2 Level DAY NIGHT AND WEEKEND MODE If Acclimate mode is not desired the FAAST system can operate in a simple day night and weekend mode This allows the device to have separa...

Страница 12: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from...

Отзывы: