background image

N.C.

N.O.

C.

Fire2 Relay

 

Contacts

(T7)

Fire Panel (FACP) typical connection 

FAAST

Fire Alarm Aspiration Sensing Technology®

FAAST

Fire Alarm Aspiration Sensing Technology®

for monitoring of device

Alarm

Short = Fire

Open = Fault

EOL

N.C.

N.O.

C.

Fire1 Relay  Contacts

(T6)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Action2

 

Rela

y

Contacts

 

(T5)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Action1 Rela

y

Contacts

 

(T4)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Alert Relay

 

Contacts

 

(T3)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Isolate Relay 

Contacts

(T10

)

Supervisory

Short = Isolate

Open = Fault

N.C.

N.O.

C.

Urgent Relay 

Contacts

(T9)

Short = Urgent Fault
Open = Fault

N.C.

N.O.

C.

Minor Relay  Contacts

 

(T8)

Short = Minor Fault

Open = Fault

N.C.

N.O.

C. (Reset)

Panel 

Remote 

Reset

-

-

+

Monitor

Short = Reset

Open = Fault

FACP

Supervisory

Supervisory

EOL

EOL

EOL

EOL

EOL

EOL

EOL

EOL

47K

FIGURE 4. FACP WIRING DIAGRAM

FIGURE 5. USER INTERFACE DISPLAY

FIGURE 6. PARTICULATE LEVEL DISPLAY

ASP18-17

ASP118-00

ASP117-00

SYSTEM POWERING

The following procedure describes how to initially power up the FAAST system.

 

1.   Unplug the unit’s power connector to the unit before turning on the power. 

 

2.  Turn on the power.

 

3.   Check the voltage at the connector. Make sure it is within the re-

quired voltage range.

 

4.   If the voltage is within the proper range, reconnect the power connec-

tor to the unit.

 

5.   Verify the system fan starts up and air begins to flow out of the ex-

haust port. The user interface will provide the device status.

 

6.   Connect a computer, with PipeIQ installed, to the unit using either 

the USB connection on the front of the device, or the Ethernet port 
located in the left side wiring door. (See the ‘Connecting to FAAST 
9400X’ for detailed connection instructions.)

 

7.   Use the PipeIQ software to set up the unit configuration required for 

the particular application.

 

8.   The PC may now be disconnected unless a permanent networked 

connection is desired. (Permanent connection of RJ45 connector is 
not allowed if used in a Class I, Division II hazardous location).

 

9.   The device will establish an airflow baseline during the first five min-

utes of operation. After five minutes, the airflow level display will 
provide the true measured airflow status. The device will give visual 
indication of the baslining period on the LCD screen.

USER INTERFACE

The user interface, shown in Figure 5, provides the following information:

•  Detector status: Normal, Alarm, General Fault, Isolate Fault, Disable 

Fault, Voltage Fault

•  Alarm Level: Alert, Action 1, Action 2, Fire 1, Fire 2

•  Particulate Level: 1 – 10 relative to Alert

•  Flow level for each pipe inlet

•  LCD for device test, service, and monitoring.

PARTICULATE LEVEL DISPLAY

The particulate level display, shown in Figure 6, consists of ten amber LEDs 
that correspond to the current level of the particulate level detected. The LEDs 
illuminate in order from Level 1 to Level 10, starting from the bottom of the 
display and moving up as the particulate level increases. Each LED represents 
a 10 percent increment in the particulate level relative to the Alert level.

 

5 ASUG56601

firealarmresources.com

Содержание XT 9400X

Страница 1: ...ipping Weight 11 8 lb 5 4 kg 1 ASUG56601 TABLE OF CONTENTS Items Included With Unit 2 Connecting to FAAST 9400X 2 Connecting to FAAST via USB 2 Connecting to FAAST via Ethernet 2 Installation 3 Pipe Installation 3 Physical Unit Installation 3 Wiring 4 User Interface 5 Particulate Level Display 5 Alarm Level Display 6 Air Flow Display 6 Fault Display 6 LCD User Interface 7 Configuration Menu Screen...

Страница 2: ...ault conditions Configurable supplementary audible indicator 2 ASUG56601 ITEMS INCLUDED WITH UNIT FAAST 9400X unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable PipeIQ software comprehensive manual and other helpful documents may be downloaded at systemsensor com faast CONNECTING TO FAAST 9400X FAAST 9400X requires a program download from PipeIQ in ord...

Страница 3: ...ropriate conduit caps from the top or bottom left side of the unit to match the orientation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the unit down onto the mounting clips and secure it with the supplied washer and nut on at least one of the two mounting studs protruding through th...

Страница 4: ...e mating connector on the unit FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS ASP114 01 CABLING REQUIREMENTS The FAAST system provides a series of Euro style pluggable terminals located behind the left side door of the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitor ing the FAAST system at a Fire...

Страница 5: ...rovide the device status 6 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring door See the Connecting to FAAST 9400X for detailed connection instructions 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 The PC may now be disconnected ...

Страница 6: ...o the next inlet every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the current air flow is to a high or low fault threshold The default threshold for a fault condition is or 20 from airflow baseline This fault threshold is configu rable using the PipeIQ so...

Страница 7: ...open Minor Fault Time Base Fault Internal Time base needs updating Minor Fault Aspirator Fault Indicates the fan has stopped working and requires immedi ate attention Urgent Fault Filter Fault Device filter is clogged and requires replacement Minor Fault Device filter is clogged and has not been replaced 72 hours af ter giving the Filter Fault with Minor Fault Relay set Urgent Fault Disable Fault ...

Страница 8: ... menu is accessed from the main menu screen with the lock feature enabled the enter password screen will be displayed The scroll keys are used to increment or decrement the number for the digit the cursor is on To enter the number use the select key and the cursor will advance to the next digit When the last digit is entered the Functions menu will be displayed if the password was entered correctl...

Страница 9: ...of the relay and the alarm settings in the device Use the scroll keys to select an option and then select key to confirm the selection RELAYS SETTINGS SCREEN The Relay Settings screen shows the latching setting for each relay A latching relaying will have an X in the box ALARM THRESHOLDS SCREEN The Alarm Thresholds screen shows the five alarm levels To get detailed in formation on an alarm level u...

Страница 10: ... performance of the de vice Therefore when creating a pipe layout the calculations that are per formed are based on the fan setting If the fan setting is changed on the device at a later date the pipe system must be re verified ALARM AND RELAY CONFIGURATION Alarm thresholds are set to default levels when shipped but are configurable Each Alarm level has its own set of form C relay contacts As the ...

Страница 11: ... Level Action 1 Action 1 High Action 1 Low Acclimate Action 1 Level Action 2 Action 2 High Action 2 Low Acclimate Action 2 Level Fire 1 Fire 1 High Fire 1 Low Acclimate Fire 1 Level Fire 2 Fire 2 High Fire 2 Low Acclimate Fire 2 Level DAY NIGHT AND WEEKEND MODE If Acclimate mode is not desired the FAAST system can operate in a simple day night and weekend mode This allows the device to have separa...

Страница 12: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from...

Отзывы: