background image

INSTALLATION

This equipment must be installed in accordance with all local and national 
codes and regulations. 

PIPE INSTALLATION

The pipe layout is designed using the PipeIQ software package. Refer to the 
Comprehensive Instruction Manual to design the pipe network. All pipe must 
be installed in accordance with local and national codes and regulations. The 
pipe network should be complete before proceeding with the physical and 
electrical system installation.

PHYSICAL UNIT INSTALLATION

WARNING

Make sure that there are no pipes or electrical wires within the wall before 
drilling any mounting holes

SECURING THE MOUNTING BRACKET

The typical mounting location for the FAAST unit is on the wall. The unit is 
mounted to the wall using the enclosed mounting plate. Figure 1 shows the 
wall mounting plate. For easier access to the FAAST unit, it is preferred to 
position the mounting plate in an easily accessible location.

 

1.   Place the mounting bracket on the wall in the desired location and 

use it as a template to locate the necessary mounting holes.

 

2.   Mark the hole locations and remove the bracket. It is recommended 

to secure the bracket using the 4 outer mounting holes. 

 

3.   Using a drill and the proper size bit for your mounting hardware, drill 

the necessary holes.

 

4.   Use appropriate fasteners to accommodate the mounting surface and 

FAAST device weight. 

 

5.  Secure the bracket to the wall.

FIGURE 1: WALL MOUNTING PLATE

ASP115-00

MOUNTING THE DETECTOR TO THE BRACKET

Once the mounting plate is attached, the unit is ready to be mounted on to the 
plate. Perform the following procedure to mount the unit.

 

1.   Before installing the unit onto the bracket, remove the appropriate 

conduit caps from the top or bottom left side of the unit to match the 
orientation of the wiring. See Figure for location of the wiring access 
plugs. 

 

2.   Line up the unit with the four mounting clips and the mounting studs 

on the left side. 

 

3.   Push the unit down onto the mounting clips and secure it with the 

supplied washer and nut on at least one of the two mounting studs 
protruding through the mounting slots shown in Figure 2.

FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS

ASP116-00

CONNECTING THE AIR SAMPLING PIPE

ATTENTION

Detailed pipe network information and best practices can be found in the Pipe 
Installation Guide, available for download at systemsensor.com/faast

The input and output ports are designed to accept nominal one inch pipe 
(25mm). The input and output ports are tapered to provide fast, easy, push-fit 
connection of the sampling pipe to the unit. Perform the following procedure 
to connect the air sampling pipe to the unit.
 

1.   Square off and de-burr the end of the sampling pipe. Ensure that the 

pipe is free from any particles that might interfere with the pipe con-
nection. 

 

2.   Remove the input plug from the input port being used (either the top 

or bottom of the unit). 

 

3.   Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT 

glue these pipes.

EXHAUST PIPE

The device must always be exhausted in to the space that it is monitoring. 
There are some circumstances where it may be necessary to connect a pipe to 
the exhaust port to divert the exhaust away from the location of the unit. Add-
ing as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensuring 
quieter operation. The output ports are tapered the same as the input ports, to 
provide fast, easy, push-fit connection of an exhaust pipe to the unit. Perform 
the following procedure to connect the exhaust pipe to the unit.

 

3 ASUG56601

firealarmresources.com

Содержание XT 9400X

Страница 1: ...ipping Weight 11 8 lb 5 4 kg 1 ASUG56601 TABLE OF CONTENTS Items Included With Unit 2 Connecting to FAAST 9400X 2 Connecting to FAAST via USB 2 Connecting to FAAST via Ethernet 2 Installation 3 Pipe Installation 3 Physical Unit Installation 3 Wiring 4 User Interface 5 Particulate Level Display 5 Alarm Level Display 6 Air Flow Display 6 Fault Display 6 LCD User Interface 7 Configuration Menu Screen...

Страница 2: ...ault conditions Configurable supplementary audible indicator 2 ASUG56601 ITEMS INCLUDED WITH UNIT FAAST 9400X unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable PipeIQ software comprehensive manual and other helpful documents may be downloaded at systemsensor com faast CONNECTING TO FAAST 9400X FAAST 9400X requires a program download from PipeIQ in ord...

Страница 3: ...ropriate conduit caps from the top or bottom left side of the unit to match the orientation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the unit down onto the mounting clips and secure it with the supplied washer and nut on at least one of the two mounting studs protruding through th...

Страница 4: ...e mating connector on the unit FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS ASP114 01 CABLING REQUIREMENTS The FAAST system provides a series of Euro style pluggable terminals located behind the left side door of the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitor ing the FAAST system at a Fire...

Страница 5: ...rovide the device status 6 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring door See the Connecting to FAAST 9400X for detailed connection instructions 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 The PC may now be disconnected ...

Страница 6: ...o the next inlet every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the current air flow is to a high or low fault threshold The default threshold for a fault condition is or 20 from airflow baseline This fault threshold is configu rable using the PipeIQ so...

Страница 7: ...open Minor Fault Time Base Fault Internal Time base needs updating Minor Fault Aspirator Fault Indicates the fan has stopped working and requires immedi ate attention Urgent Fault Filter Fault Device filter is clogged and requires replacement Minor Fault Device filter is clogged and has not been replaced 72 hours af ter giving the Filter Fault with Minor Fault Relay set Urgent Fault Disable Fault ...

Страница 8: ... menu is accessed from the main menu screen with the lock feature enabled the enter password screen will be displayed The scroll keys are used to increment or decrement the number for the digit the cursor is on To enter the number use the select key and the cursor will advance to the next digit When the last digit is entered the Functions menu will be displayed if the password was entered correctl...

Страница 9: ...of the relay and the alarm settings in the device Use the scroll keys to select an option and then select key to confirm the selection RELAYS SETTINGS SCREEN The Relay Settings screen shows the latching setting for each relay A latching relaying will have an X in the box ALARM THRESHOLDS SCREEN The Alarm Thresholds screen shows the five alarm levels To get detailed in formation on an alarm level u...

Страница 10: ... performance of the de vice Therefore when creating a pipe layout the calculations that are per formed are based on the fan setting If the fan setting is changed on the device at a later date the pipe system must be re verified ALARM AND RELAY CONFIGURATION Alarm thresholds are set to default levels when shipped but are configurable Each Alarm level has its own set of form C relay contacts As the ...

Страница 11: ... Level Action 1 Action 1 High Action 1 Low Acclimate Action 1 Level Action 2 Action 2 High Action 2 Low Acclimate Action 2 Level Fire 1 Fire 1 High Fire 1 Low Acclimate Fire 1 Level Fire 2 Fire 2 High Fire 2 Low Acclimate Fire 2 Level DAY NIGHT AND WEEKEND MODE If Acclimate mode is not desired the FAAST system can operate in a simple day night and weekend mode This allows the device to have separa...

Страница 12: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from...

Отзывы: