background image

 

1.   Square off and de-burr the end of the sampling pipe. Ensure that the 

pipe is free from any particles that might interfere with the pipe con-
nection. 

 

2.   Remove the input plug from the input port being used (either the top 

or bottom of the unit). 

 

3.   Insert the air sampling pipe into the port, ensuring a snug fit.  

DO NOT glue these pipes.

WIRING

WARNING

Before working on the FAAST system, notify all required authorities that the 
system will be temporarily out of service. Make sure all power is removed 
from the system before opening the unit. All wiring must be in accordance 
with local codes.

POWER CABLES

Use the power ratings of the unit to determine the required wire sizes for each 
connection. Use the power ratings of the connected products to determine the 
wire size. 

CONDUIT USAGE

If electrical conduit is used for system wiring, terminate the conduits at the 
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.

 

1.   Run all wiring, both power and alarm, through the conduit and into 

the left side of the unit enclosure, as seen in Figure 3.

 

2.   Attach the appropriate wires to the supplied Euro connector. Follow 

appropriate local codes and electrical standards for all cabling.

 

3.  Plug the appropriate connector into the mating connector on the unit.

FIGURE 3. POWER AND ALARM CONNECTION BLOCK

TABLE 1. TERMINAL DESIGNATIONS

ASP114-01

CABLING REQUIREMENTS

The FAAST system provides a series of Euro style pluggable terminals, located 
behind the left side door of the unit. Refer to Table 1 for the proper electrical 
connections to the unit. Refer to Table 2 for a typical connection for monitor-
ing the FAAST system at a Fire Alarm Control Panel (FACP).

NAME

TERMINAL BLOCK

NOTES

External Power -

T1

Powers Aspirating 
Smoke Detector

External Power -

External Power +

External Power +

SLC +

T2

Not used on  
conventional models

SLC +

SLC -

SLC -

A IN

T3

RS-485 Rx

C

Rx and Tx can be 
wired in a half duplex 
configuration

B IN

A OUT

T4

RS-485 Tx

C

Rx and Tx can be 
wired in a half duplex 
configuration

B OUT

Alert NO

T5

Maintains state on loss 
of power

Alert COM

 

Alert NC

 

Action 1 NO

T6

Maintains state on loss 
of power

Action 1 COM

 

Action 1 NC

 

Action 2 NO

T7

Maintains state on loss 
of power

Action 2 COM

 

Action 2 NC

 

Fire 1 NO

T8

Maintains state on loss 
of power

Fire 1 COM

 

Fire 1 NC

 

Fire 2 NO

T9

Maintains state on loss 
of power

Fire 2 COM

 

Fire 2 NC

 

Minor Fault NO

T10

Maintains state on loss 
of power

Minor Fault COM

 

Minor Fault NC

 

Urgen Fault NC

T11

Always reverts to reset 
on loss of power

Urgent Fault COM

NO, NC designations 
are with power applied 
and unit operating 
without fault.

Urgent Fault NO

 

Isolate NO

T12

Isolate COM

Isolate NC

 

External Monitor

T13

 

4 ASUG56601

firealarmresources.com

Содержание XT 9400X

Страница 1: ...ipping Weight 11 8 lb 5 4 kg 1 ASUG56601 TABLE OF CONTENTS Items Included With Unit 2 Connecting to FAAST 9400X 2 Connecting to FAAST via USB 2 Connecting to FAAST via Ethernet 2 Installation 3 Pipe Installation 3 Physical Unit Installation 3 Wiring 4 User Interface 5 Particulate Level Display 5 Alarm Level Display 6 Air Flow Display 6 Fault Display 6 LCD User Interface 7 Configuration Menu Screen...

Страница 2: ...ault conditions Configurable supplementary audible indicator 2 ASUG56601 ITEMS INCLUDED WITH UNIT FAAST 9400X unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable PipeIQ software comprehensive manual and other helpful documents may be downloaded at systemsensor com faast CONNECTING TO FAAST 9400X FAAST 9400X requires a program download from PipeIQ in ord...

Страница 3: ...ropriate conduit caps from the top or bottom left side of the unit to match the orientation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the unit down onto the mounting clips and secure it with the supplied washer and nut on at least one of the two mounting studs protruding through th...

Страница 4: ...e mating connector on the unit FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS ASP114 01 CABLING REQUIREMENTS The FAAST system provides a series of Euro style pluggable terminals located behind the left side door of the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitor ing the FAAST system at a Fire...

Страница 5: ...rovide the device status 6 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring door See the Connecting to FAAST 9400X for detailed connection instructions 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 The PC may now be disconnected ...

Страница 6: ...o the next inlet every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the current air flow is to a high or low fault threshold The default threshold for a fault condition is or 20 from airflow baseline This fault threshold is configu rable using the PipeIQ so...

Страница 7: ...open Minor Fault Time Base Fault Internal Time base needs updating Minor Fault Aspirator Fault Indicates the fan has stopped working and requires immedi ate attention Urgent Fault Filter Fault Device filter is clogged and requires replacement Minor Fault Device filter is clogged and has not been replaced 72 hours af ter giving the Filter Fault with Minor Fault Relay set Urgent Fault Disable Fault ...

Страница 8: ... menu is accessed from the main menu screen with the lock feature enabled the enter password screen will be displayed The scroll keys are used to increment or decrement the number for the digit the cursor is on To enter the number use the select key and the cursor will advance to the next digit When the last digit is entered the Functions menu will be displayed if the password was entered correctl...

Страница 9: ...of the relay and the alarm settings in the device Use the scroll keys to select an option and then select key to confirm the selection RELAYS SETTINGS SCREEN The Relay Settings screen shows the latching setting for each relay A latching relaying will have an X in the box ALARM THRESHOLDS SCREEN The Alarm Thresholds screen shows the five alarm levels To get detailed in formation on an alarm level u...

Страница 10: ... performance of the de vice Therefore when creating a pipe layout the calculations that are per formed are based on the fan setting If the fan setting is changed on the device at a later date the pipe system must be re verified ALARM AND RELAY CONFIGURATION Alarm thresholds are set to default levels when shipped but are configurable Each Alarm level has its own set of form C relay contacts As the ...

Страница 11: ... Level Action 1 Action 1 High Action 1 Low Acclimate Action 1 Level Action 2 Action 2 High Action 2 Low Acclimate Action 2 Level Fire 1 Fire 1 High Fire 1 Low Acclimate Fire 1 Level Fire 2 Fire 2 High Fire 2 Low Acclimate Fire 2 Level DAY NIGHT AND WEEKEND MODE If Acclimate mode is not desired the FAAST system can operate in a simple day night and weekend mode This allows the device to have separa...

Страница 12: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from...

Отзывы: