SPECIFICATIONS

Electrical Characteristics

External Supply Voltage 

18 – 30 VDC

Remote Reset Time 

External monitor must be pulled low 

 

for a minimum of 100 msec

Power Reset 

1 sec

Average Operating Current 

Fan High – 465mA, 11.2W

 

Fan Med – 340mA, 8.2W

 

Fan Low – 220mA, 5.3W

Alarm Current 

Fan High – 493mA, 11.85W

 

Fan Med – 368mA, 8.85W

 

Fan Low – 248mA, 6W

Relay Contact Ratings 

3.0A @ 30VDC, 0.5A @125VAC

Environmental Ratings

Operating Temperature 

32°F (0°C) to 100°F (38°C) – 

 

Factory tested to 131°F (55°C)

Sampled Air Temperature 

-4°F (-20°C) to 140°F (160°C)

Humidity 

10 to 95% non-condensing

IP Rating 

IP30

Coverage Area 

28,800 sq.ft. (2,676 sq.m.)

Air Movement 

0 – 4,000 ft/min (0 – 1,219.2 m/min)

FAAST XT 9400X
Fire Alarm Aspiration Sensing Technology

®

COMPREHENSIVE USER GUIDE

Exterior Dimensions

Height 

13.3 in (338 mm)

Width 

13.1 in (333 mm)

Depth 

7.5 in (191mm)

Cable Access 

4 1in (25.4mm) cable 

 

access holes on top, 

 

bottom and back of unit

Wire Gauge 

12 Ga.

Pipe Size 

½ or ¾ in Nom.

 

(20 or 25mm Nom.)

Max Single Pipe Length 

400 feet (123 m) 

 *

other three pipes disabled

Total Pipe Length 

1050 ft. (320 m) 

 *

designs must be verified

 

 within PipeIQ software

Shipping Weight 

11.8 lb (5.4 kg)

 

1 ASUG56601

TABLE OF CONTENTS

Items Included With Unit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting to FAAST 9400X  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting to FAAST via USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting to FAAST via Ethernet   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Pipe Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Unit Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Wiring 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

User Interface   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Particulate Level Display   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Alarm Level Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Air Flow Display  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fault Display  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LCD User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Configuration Menu Screen   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
LCD Menu Screen   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Language Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Backlight Screen   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Contrast Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Message Log Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Set Time Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Special mode screens  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Initialization Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Baselining Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Firmware Upgrade Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Modes of Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Initialization  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Configuration Overview  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Fan Speed Configuration   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Alarm and Relay Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Audible Indicator Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Failure of Configuration validation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power glitch during configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Normal 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Test 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Sounder Test  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Reset 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Reset Airflow Baselines   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Isolation 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Disable Mode   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Acclimate Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Day, Night And Weekend Mode   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Logs 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Event Log    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Data Trend Log   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Message Log  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
External Monitor/Reset   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Ethernet Connection   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
USB Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Pipe Network   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Web Server    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Email Notification  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Canned Smoke Testing  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Laser Safety Information   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Warranty  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FCC Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

firealarmresources.com

Содержание XT 9400X

Страница 1: ...ipping Weight 11 8 lb 5 4 kg 1 ASUG56601 TABLE OF CONTENTS Items Included With Unit 2 Connecting to FAAST 9400X 2 Connecting to FAAST via USB 2 Connecting to FAAST via Ethernet 2 Installation 3 Pipe Installation 3 Physical Unit Installation 3 Wiring 4 User Interface 5 Particulate Level Display 5 Alarm Level Display 6 Air Flow Display 6 Fault Display 6 LCD User Interface 7 Configuration Menu Screen...

Страница 2: ...ault conditions Configurable supplementary audible indicator 2 ASUG56601 ITEMS INCLUDED WITH UNIT FAAST 9400X unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable PipeIQ software comprehensive manual and other helpful documents may be downloaded at systemsensor com faast CONNECTING TO FAAST 9400X FAAST 9400X requires a program download from PipeIQ in ord...

Страница 3: ...ropriate conduit caps from the top or bottom left side of the unit to match the orientation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the unit down onto the mounting clips and secure it with the supplied washer and nut on at least one of the two mounting studs protruding through th...

Страница 4: ...e mating connector on the unit FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS ASP114 01 CABLING REQUIREMENTS The FAAST system provides a series of Euro style pluggable terminals located behind the left side door of the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitor ing the FAAST system at a Fire...

Страница 5: ...rovide the device status 6 Connect a computer with PipeIQ installed to the unit using either the USB connection on the front of the device or the Ethernet port located in the left side wiring door See the Connecting to FAAST 9400X for detailed connection instructions 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 The PC may now be disconnected ...

Страница 6: ...o the next inlet every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the current air flow is to a high or low fault threshold The default threshold for a fault condition is or 20 from airflow baseline This fault threshold is configu rable using the PipeIQ so...

Страница 7: ...open Minor Fault Time Base Fault Internal Time base needs updating Minor Fault Aspirator Fault Indicates the fan has stopped working and requires immedi ate attention Urgent Fault Filter Fault Device filter is clogged and requires replacement Minor Fault Device filter is clogged and has not been replaced 72 hours af ter giving the Filter Fault with Minor Fault Relay set Urgent Fault Disable Fault ...

Страница 8: ... menu is accessed from the main menu screen with the lock feature enabled the enter password screen will be displayed The scroll keys are used to increment or decrement the number for the digit the cursor is on To enter the number use the select key and the cursor will advance to the next digit When the last digit is entered the Functions menu will be displayed if the password was entered correctl...

Страница 9: ...of the relay and the alarm settings in the device Use the scroll keys to select an option and then select key to confirm the selection RELAYS SETTINGS SCREEN The Relay Settings screen shows the latching setting for each relay A latching relaying will have an X in the box ALARM THRESHOLDS SCREEN The Alarm Thresholds screen shows the five alarm levels To get detailed in formation on an alarm level u...

Страница 10: ... performance of the de vice Therefore when creating a pipe layout the calculations that are per formed are based on the fan setting If the fan setting is changed on the device at a later date the pipe system must be re verified ALARM AND RELAY CONFIGURATION Alarm thresholds are set to default levels when shipped but are configurable Each Alarm level has its own set of form C relay contacts As the ...

Страница 11: ... Level Action 1 Action 1 High Action 1 Low Acclimate Action 1 Level Action 2 Action 2 High Action 2 Low Acclimate Action 2 Level Fire 1 Fire 1 High Fire 1 Low Acclimate Fire 1 Level Fire 2 Fire 2 High Fire 2 Low Acclimate Fire 2 Level DAY NIGHT AND WEEKEND MODE If Acclimate mode is not desired the FAAST system can operate in a simple day night and weekend mode This allows the device to have separa...

Страница 12: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from...

Отзывы: