The states of all inputs on the 460P card terminal block (inputs 1-5) and on the MEI
module if present (inputs 6-11) are displayed in real time.
By activating the activation device connected to each input it is possible to
verify operation by noting the change in status of the symbol alongside:
= Contact open
= Contact closed
N.B.:
1) The inputs are numbered according to the physical layout of the terminal
block without taking account of the meaning assigned to them. The correctness
of the state of the input must be determined according to the function assigned
to the terminal.
2) When the Gatecoder is used, the respective input shows a sequence of con-
tact open/closed states when the gate is moving.
Press ENTER to proceed.
ENTER
9.
DIAGNOSTICS
ENTER
CONNECT TO 460P
AND PRESS ENTER
CHECK VOLTAGES
Vbat +Vrl +5V Vacc
^
^
^
^
OK
OK
OK
OK
ENTER
12
The FAACTOTUM checks the following voltages:
Vbat = FAACTOTUM internal battery voltage
Vrl = 460P card relay power supply voltage (12Vdc)
+5V = 460P card logic power supply voltage (5Vdc)
Vacc = Accessories power supply voltage (24Vdc)
The message OK appears next to each correct voltage.
If this message does not appear for one or more voltages, this means that the
measured voltage is lower than it should be or is absent.
For further information, read chapter 11 “Checking voltages”.
ENTER
To perform complete diagnostics on the automation, the FAACTOTUM must be
connected to the 460P electronic control unit.
Press ENTER to continue.
ENTER
The menus contained in the diagnostics (with the exception of the voltage check menu) are shown
only if the FAACTOTUM is connected to the card.
These menus provide valuable assistance for checking the functionality of the system and for diagnostics,
and also provide information on the degree of usage of the automation.
SOFTWARE VERSION
460P
X.X
The 460P card software version is shown.
Press ENTER to continue.
ENTER
During installation, before performing the time learning cycle, it is advisable to check that the
automation is working correctly by performing the motor check.
The by-pass valves should also be regulated by following the specific instructions for the hydraulic
operator.
➲
INPUT STATES
1 2 3 4 5
6 7 8 9 10 11
ENTER
The following information is displayed in real time:
1) STATE
= State of the automation
The envisaged states are:
-CLOSED
= Gate closed
-PREFL.OPEN
= Opening pre-flashing
-OPENING
= Gate opening
-OPEN TMP
= Timed opening (operation of closure safety edge)
-OPEN
= Gate open
-PAUSE
= Gate on pause
-PREFL.CLOS
= Closure pre-flashing
-CLOSING
= Gate closing
-CLOS.TMP
= Timed closure (operation of opening safety edge)
-STOP OPEN
= Stops then opens
-STOP CLOS.
= Stops then closes
-STOP FSW-C
= Closure safety tripped
-STOP FSW-O
= Opening safety tripped
-PANIC
= Panic opening device control activated
-PROGRAMM.
= Programming
ENTER
GATE STATE
STATE
CLOSED
LAMP
OFF
OUT F.TX
ON
RX OK
ENTER
ENTER
(cont.)
(cont.)