INSTRUCTION MANUAL FOR DAAB EP104 CONTROL BOARD
Error messages
E-code
Meaning
Possible cause
EP-1
Not an error code – indicates the type of EP104
in use
EP-2
Not an error code – indicates the type of EP104
in use
E000
No error, shown to acknowledge a change in the
service channel.
E003
Limited running time exceeded
Gears slipping? Check C403
E008
Momentary loss of 24 V
Mains failure, momentary 24 V short circuit.
E015
Momentary loss of 230V
Has there been a power failure?
E017
Safety edge or load guard triggered five times in
succession
It something preventing the door reaching the closed
position?
E020
Voltage too high in safety circuit
The voltage measured by the automatic control unit is too
high.
E025
Incorrect setting for personal protection, motor 1
Check C200 and C230, the load guard cannot be disabled
with personal protection activated. Check C211, it cannot
be longer than 0.06 sec. C212 cannot be longer than 2 sec.
C493 cannot be longer than 0.20 sec.
E026
Incorrect setting for personal protection, motor 2
Check C200 and C240, the load guard cannot be disabled
with personal protection activated. Check C211, it cannot
be longer than 0.06 sec. C212 cannot be longer than 2 sec.
C493 cannot be longer than 0.20 sec.
E032
Limit switch L.O1 has lost its position
Is the limit switch cam bypassing the switch? Loose contact
in switch?
E033
Limit switch L.C1 has lost its position
Is the limit switch cam bypassing the switch? Loose contact
in switch?
E042
Limit switch L.O2 has lost its position
Is the limit switch cam bypassing the switch? Loose contact
in switch?
E043
Limit switch L.C2 has lost its position
Is the limit switch cam bypassing the switch? Loose contact
in switch?
E044
Hidden channels shown
E046
Opening counter reset
E047
Factory reset of all channels
E048
Error code list reset
E116
No safety edge acknowledgement
Only applies to up-and-over control, fault in safety edge?
Correct run-on time?
E201
Motor protection triggered for motor 1
Motor is taking more than 1.5x motor current. Motor is
sluggish or stops. Faulty fuse? Phase failure in an incoming
phase? Break in cable to motor or motor winding? Check the
motor protection setting.
E202
Motor protection triggered for motor 2
E203
Motor protection triggered three times in a row,
control unit locked for three minutes
Is there an obstacle? Fault in electric motor? Check the
configuration of channels C252, C253, C262, C263.
E204
Current through motor 1, which is switched off
E205
Current through motor 2, which is switched off
E206
No current or low current in motor 1
The electric motor is running at less than half the motor
protection setting. Check the motor protection setting.
Phase failure in an incoming phase? Faulty fuse? Break in
cable to electric motor? Voltage drop in stop circuit/limit
switch circuit? (Prevents the contactors operating.)
E207
No current or low current in motor 2
E221
Start load too low, motor 1
Check that the motor is correctly connected.
E222
Start load too low, motor 2
Check that the motor is correctly connected.
E223
Normal power too low, motor 1
Check C230.