16
ENGLISH
26
When this function is activated, the
CLOSING SAFETIES
during closing stop and reverse
movement when they are disengaged, otherwise they reverse immediately.
Y
= stops and reverses when
disengaged.
no
= reverses immediately.
27
DO NOT CHANGE
no
28
DO NOT CHANGE
no
29
DO NOT CHANGE
no
30
When this function is activated, the
LOOP1
commands are prioritised rather than the
LOOP2
commands.
Y
= active
no
= disabled
A0
HOLD CLOSE / HOLD OPEN function
When this function is activated, the automated system will monitor the position of the beam
at
set intervals (see parameter
A 1
). If the beam is not completely closed or completely
open
(depending on the logical condition of the board), the automated system will command
a CLOSE or OPEN movement to bring the beam back to the correct position, for a maximum
of 3 seconds. If, when the 3 seconds have elapsed, the bar does not go back to completely
closed/open position (e.g. because the bar is blocked), the function will be disabled until the
next OPEN command is received.
Y
A 1
HOLD CLOSE / HOLD OPEN function activation time
This parameter indicates the time interval between two activations of the HOLD OPEN /
HOLD CLOSE function, expressed in minutes. (from
00
to
99
)
60
r 1
Loop 1 frequency reading
This menu item lets you verify the reading of the current oscillation frequency of the loop
connected to the Loop 1 input. The indication should be read as follows:
First digit: tens (kHz)
Second digit: units (kHz)
Decimal point: hundreds (kHz)
For example, the reading
05
.
refers to a reading of 105 kHz
Read-only parameter
r 2
Loop 2 frequency reading
This menu item lets you verify the reading of the current oscillation frequency of the loop
connected to the Loop 2 input. (see parameter
r1
for explanations on how to read the
indicated value)
Read-only parameter
F 1
Loop 1 frequency selection
This parameter lets you set an oscillation frequency specific to the loop connected to the
Loop 1 input, or lets the system choose the most adequate setting among the 4 available.
A
Automatic selection
1-2-3-4
Frequency 1-2-3-4
Note:
When you exit the Advanced configuration menu after having changed the loop
operation frequency setting, the system will be recalibrated. This will provide an updated
frequency reading once you re-enter the menu to consult the values of parameters
r1
or
r2
A
F 2
Loop 2 frequency selection
This parameter lets you set an oscillation frequency specific to the loop connected to the
Loop 2 input, or lets the system choose the most adequate setting among the 4 available.
A
Automatic selection
1-2-3-4
Frequency 1-2-3-4
Note:
When you exit the Advanced configuration menu after having changed the loop
operation frequency setting, the system will be recalibrated. This will provide an updated
frequency reading once you re-enter the menu to consult the values of parameters
r1
or
r2
A
Содержание B680H
Страница 1: ...B680H ...
Страница 2: ......
Страница 4: ......
Страница 150: ...26 a b DX SX a b c Fig 10 Fig 11 M M L1 L2 L3 L1 L2 L3 Fig 12 d Fig 13 Fig 14 Fig 15 a b Fig 16 ...
Страница 151: ...27 a b c d e f g h Fig 17 L ...
Страница 152: ...28 Fig 18 a b a b d Fig 19 c 1 2 Fig 20 ...
Страница 153: ...29 a b Fig 21 d e f c ...
Страница 156: ...32 Fig 31 a b c d e ...
Страница 157: ...33 Fig 32 f g ...
Страница 158: ......
Страница 163: ...5 1 2 Fig 18 ...
Страница 164: ......
Страница 165: ......