A952 55
532310 - Rev.A
2
ADVANCED programming
ADVANCED programming
Default
S1
SIDE FUNCTIONS SELECTOR POSITION 1
Defines the function of the external selector when
in position 1
no = DISABLED
1 = NIGHT
2 = OPENED
3 = EXIT ONLY
4 = MANUAL
2
S2
SIDE FUNCTIONS SELECTOR POSITION 2
Defines the function of the selector when in position 2
See parameter
S1
.
4
O1
OUTPUT CONFIGURATION OUT 1
0 = DISABLED
1 = GONG
2 = ERROR
3 = BATTERY OPERATION
4 = EMERGENCY ACTIVE
5 = TEST
6 = DOOR NOT CLOSED
7 = DOOR OPENED
8 = DOOR OPENING
9 = courtesy LIGHT
10 = INTRUSION ACTIVE
11 = CLOSING SAFETY ACTIVE
12 = SAFETIES ACTIVE
16 = Simply Connect PROGRAMMING in PROGRESS
18 = PEOPLE IN NUMBER
19 = RED TRAFFIC LIGHT EXT
20 = GREEN TRAFFIC LIGHT EXT
21 = RED TRAFFIC LIGHT INT
22 = GREEN TRAFFIC LIGHT INT
23 = LOW BATTERY
1
1C
CONTACT TYPE - OUTPUT OUT 1
Not displayed if output is disabled
nO
= NO contact
nC
= NC contact
nO
O2
OUTPUT CONFIGURATION OUT 2
See
O1
5
2C
CONTACT TYPE - OUTPUT OUT 2
See
1C
nC
O3
OUTPUT CONFIGURATION OUT 3
See
O1
7
3C
CONTACT TYPE - OUTPUT OUT 3
See
1C
nO
O4
OUTPUT CONFIGURATION OUT 4
See
O1
6
4C
CONTACT TYPE - OUTPUT OUT 4
See
1C
nO
ADVANCED programming
Default
O5
OUTPUT CONFIGURATION OUT 5
See
O1
18
5C
CONTACT TYPE - OUTPUT OUT 5
See
1C
nO
CF
CLOSING STRENGTH
Adjustable from 1 (minimum) to 10 (MAX)
5
OF
OPENING STRENGTH
Adjustable from 1 (minimum) to 10 (MAX)
10
to
OP. STRENGTH DURATION
Regulates the maximum thrust time before an obstacle
is recognised during opening
Adjustable from 1 to 30 tenths of a second
15
tc
CL. STRENGTH DURATION
Regulates the maximum thrust time before an obstacle
is recognised during closing
Adjustable from 1 to 30 tenths of a second
15
Hc
ANTI-INTRUSION
The door resists attempts to open it manually
no
= disabled
Y
= enabled
no
!
DO NOT enable this function if the door is used as
an escape route.
cS
SCP (SELECTABLE CLOSE POWER)
Increases the force with which the door pushes in the
final section of the closure. It is useful to activate
this function if there is high friction, if the seals are
particularly rigid or if locks have a stiff latch.
no
= disabled
Y
= enabled
no
!
Because activating the SCP function also reduces the
sensitivity of the electronic anti-crushing system in
the final section of closing, DO NOT activate the SCP
function in "LOW ENERGY" mode.
EL
MOTOR LOCK (lock)
0 = disabled
1 = active in NIGHT mode
2 = active in EXIT ONLY mode
3 = active in NIGHT + ONE-WAY mode
4 = ALWAYS active
0
Et
OPENING DELAY after LOCK ACTIVATION
Defines the opening delay time of the door to allow the
lock to be released, particularly the motorised ones.
Adjustable from
0
to
60
tenths of a second
3