Operating Manual
58
11.4 System Run Times
The table below shows system run times with various loads for a 24V system (using
1x iBATT100 Enclosure) and a 48V system (using 2x iBATT100 Enclosures).
System
run times are when using new batteries and are based on battery manufacturer’s data at
20ºC discharging to 1.7Vpc
Load (VA)
Total run time
24V System
(mins)
Total run time
48V System
(mins)
3000
39
87
2500
50
108
2000
70
146
1500
90
205
1000
154
336
500
336
857
Important!
Whilst accurate to the best of our knowledge, Extronics cannot be held
responsible for any discrepancies. System wiring, battery ageing, and
temperature all have an influence on run times. Above 20ºC system run
times will marginally improve, and below this temperature they will
decrease.